Date |
Text |
2019-08-29 15:37:04 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| |
| PLUMBING COMMEMTS: DENIED |
| |
| 1 AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| DESIGNER PER WPB FBC 107.2.1. |
| |
| 2. RE: PLAN SHEET P-1; SANITARY RISER DIAGRAM. IF THE |
| EXISTING WASHER IS CONNECTED TO A TWO STACK WITH REVENT |
| SYSTEM THEN (1) NEW WASHER DRAIN SHALL CONNECT TO |
| EXISTING WASTE STACK, NOT TO THE VENT AND (2) A VENT |
| SHALL BE PROVIDED AT THE POINT THAT THE TRAPPED WASHER |
| DRAIN CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL |
| CONNECT TO THE EXISTING VENT STACK (FBC PL 905.1). IF |
| THE EXISTING WASHER CONNECTS TO A SINGLE PIPE WASTE |
| STACK VENT FBC PL 913), THEN A VENT SHALL BE PROVIDED |
| AT THE POINT THAT THE TRAPPED CLOTHES WASHER DRAIN |
| CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL CONNECT |
| TO AN EXISTING BRANCH VENT OR VENT STACK (FBC PL |
| 905.1). IF AN EXISTING BRANCH VENT OR VENT STACK IS NOT |
| AVAILABLE, THE NEW HORIZONTAL DRAIN SHALL BE SIZED 3? |
| (AS REQUIRED BY MANUFACTURER OF AIR ADMITTANCE VALVE |
| INSTALLATION GUIDE) TO THE POINT OF HORIZONTAL TO |
| VERTICAL THEN CAN BE 2? SIZE. AN AIR ADMITTANCE VALVE |
| SHALL BE INSTALLED ABOVE THE POINT THAT THE TRAPPED |
| CLOTHES WASHER DRAIN CHANGES FROM HORIZONTAL TO |
| VERTICAL. PER WPB FBC 107.2.1, CONFIRM WHICH TYPE OF |
| WASTE AND VENT SYSTEM IS INVOLVED, THE SIZES OF THE |
| EXISTING AND SHOW ON THE SANITARY RISER DIAGRAM. |
| SPECIFY THE TYPE OF MATERIAL USED FOR NEW AND EXISTING |
| PIPING, I.E. PVC DWV, CAST IRON, ETC. |
| |
| 3. RE: PLAN SHEET P-1; SHOWER DETAIL. PROVIDE ON THE |
| ELEVATION CUT THROUGH DETAIL OF THE SHOWER COMPARTMENT |
| (FBC PL 417.5 THROUGH 417.5.2.6) THE TYPE OF LINER, THE |
| HEIGHT ABOVE THE CURB IT EXTENDS, EXISTING SLAB |
| THICKNESS AND THE TYPE OF MATERIAL USED FOR NEW AND |
| EXISTING PIPING, I.E. PVC DWV, CAST IRON, ETC. |
| |
| 4. PROVIDE UL FIRE SAFING DETAIL(S) FOR THROUGH THE |
| FLOOR PIPE PENETRATIONS. COMPLY WITH THE REQUIREMENTS |
| OF FBC CHAPTER 7. |
| |
| 5. PROVIDE ANTI-SCALD VALVES IN ALL SHOWERS PER FBC PL |
| 424.3. |
| |
| 6. PROVIDE WATER HAMMER ARRESTORS CONFORMING TO ASSA |
| 1010 AT DISHWASHER, REFRIGERATOR ICE LINE AND CLOTHES |
| WASHER PER FBC PL 604.9 |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19080396 2425 PRESIDENTIAL WAY 403 |
| |