Plan Review Notes
Plan Review Notes For Permit 19080396
Permit Number 19080396
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-29 15:37:04CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
  
 PLUMBING COMMEMTS: DENIED
  
 1 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
 2. RE: PLAN SHEET P-1; SANITARY RISER DIAGRAM. IF THE
 EXISTING WASHER IS CONNECTED TO A TWO STACK WITH REVENT
 SYSTEM THEN (1) NEW WASHER DRAIN SHALL CONNECT TO
 EXISTING WASTE STACK, NOT TO THE VENT AND (2) A VENT
 SHALL BE PROVIDED AT THE POINT THAT THE TRAPPED WASHER
 DRAIN CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL
 CONNECT TO THE EXISTING VENT STACK (FBC PL 905.1). IF
 THE EXISTING WASHER CONNECTS TO A SINGLE PIPE WASTE
 STACK VENT FBC PL 913), THEN A VENT SHALL BE PROVIDED
 AT THE POINT THAT THE TRAPPED CLOTHES WASHER DRAIN
 CHANGES FROM HORIZONTAL TO VERTICAL AND SHALL CONNECT
 TO AN EXISTING BRANCH VENT OR VENT STACK (FBC PL
 905.1). IF AN EXISTING BRANCH VENT OR VENT STACK IS NOT
 AVAILABLE, THE NEW HORIZONTAL DRAIN SHALL BE SIZED 3?
 (AS REQUIRED BY MANUFACTURER OF AIR ADMITTANCE VALVE
 INSTALLATION GUIDE) TO THE POINT OF HORIZONTAL TO
 VERTICAL THEN CAN BE 2? SIZE. AN AIR ADMITTANCE VALVE
 SHALL BE INSTALLED ABOVE THE POINT THAT THE TRAPPED
 CLOTHES WASHER DRAIN CHANGES FROM HORIZONTAL TO
 VERTICAL. PER WPB FBC 107.2.1, CONFIRM WHICH TYPE OF
 WASTE AND VENT SYSTEM IS INVOLVED, THE SIZES OF THE
 EXISTING AND SHOW ON THE SANITARY RISER DIAGRAM.
 SPECIFY THE TYPE OF MATERIAL USED FOR NEW AND EXISTING
 PIPING, I.E. PVC DWV, CAST IRON, ETC.
  
 3. RE: PLAN SHEET P-1; SHOWER DETAIL. PROVIDE ON THE
 ELEVATION CUT THROUGH DETAIL OF THE SHOWER COMPARTMENT
 (FBC PL 417.5 THROUGH 417.5.2.6) THE TYPE OF LINER, THE
 HEIGHT ABOVE THE CURB IT EXTENDS, EXISTING SLAB
 THICKNESS AND THE TYPE OF MATERIAL USED FOR NEW AND
 EXISTING PIPING, I.E. PVC DWV, CAST IRON, ETC.
  
 4. PROVIDE UL FIRE SAFING DETAIL(S) FOR THROUGH THE
 FLOOR PIPE PENETRATIONS. COMPLY WITH THE REQUIREMENTS
 OF FBC CHAPTER 7.
  
 5. PROVIDE ANTI-SCALD VALVES IN ALL SHOWERS PER FBC PL
 424.3.
  
 6. PROVIDE WATER HAMMER ARRESTORS CONFORMING TO ASSA
 1010 AT DISHWASHER, REFRIGERATOR ICE LINE AND CLOTHES
 WASHER PER FBC PL 604.9
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080396 2425 PRESIDENTIAL WAY 403
  