Plan Review Notes
Plan Review Notes For Permit 19080396
Permit Number 19080396
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-26 13:29:332017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080396
 ADD: 2425 PRESIDENTIAL WAY SUITE: 403
 CONT: O & D TOTAL HOME REPAIR CORP.
 TEL: 561-969-3121
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 26/ 2019
 ACTION: DENIED
  
 1) SHEET 1-1 UNDER THE HEADING DESIGN CRITERIA:
 1A) THE PLAN INDICATES THE CONSTRUCTION TYPE AS V-B.
 PLEASE NOTE THIS SUITE IS LOCATED IN A HIGHRISE
 BUILDING AND BUILDING TYPE IS TYPE I-A. SEE THE 2017
 FBC-B TABLE 504.4.
  
 1B) THE SHEET 1-1 UNDER THE HEADING OF DESIGN CRITERIA
 LIST THE OCCUPANCY TYPE AS A R-3. PLEASE NOTE MOST R-3
 ARE SINGLE FAMILY RESIDENCES. FEW R-3 ARE A MIXED
 OCCUPANCY WHERE IS A BUSINESS OR MERCANTILE ON THE 1ST
 FLOOR AND A SINGLE DWELLING UNIT ON THE 2ND FLOOR.
 APARTMENT BUILDINGS AND CONDOMINIUMS THAT ARE PRIMARILY
 PERMANENT IN NATURE ARE CONSIDERED OCCUPANCY TYPE R2.
 PLEASE REVIEW THE 2017 FBC-B 310.2.
  
 2) PLEASE NOTE THE SUBMITTED SALES BROCHURE DOES NOT
 HAVE THE CORRECT DATA AND TESTING RESULTS TO OBTAIN A
 PERMIT. WE HAVE TO DATE NOT PERMITTED THE PRODUCT SAM
 90 CONTROL MEMBRANE. WE DO HAVE THE ACTUAL TEST RESULT
 THAT HAVE PASSED FOR SUPER SAM125.
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL
 NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR
 ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE
 QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A
 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND.
 WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES
 SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM
 PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION
 CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED)
 FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM
 E 90.
  
 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 3) IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO
 ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY
 TO COMPLY WITH THE STATE & FEDERAL ASBESTOS
 REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61-
 NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS
 SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: *
 DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  