Plan Review Notes
Plan Review Notes For Permit 19080390
Permit Number 19080390
Review Stop E
Sequence Number 1
Notes
Date Text
2019-08-26 07:55:30FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) NEED TO SUBMIT A RISER DIAGRAM PER 215.5
  
 2) NEED TO SUBMIT PANEL SCHEDULE(S)
  
 3) NEED TO COMPLY WITH THE ENERGY CODE FOR LIGHTING
 CONTROL AND RECEPTACLE CONTROL
  
 4) NEED TO SUBMIT A LOAD CALCULATION PER ARTICLE 220 OF
 THE NEC.