Plan Review Notes For Permit 19080390 |
Permit Number |
19080390 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-26 07:55:30 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY BN, BU, PX | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | 1) NEED TO SUBMIT A RISER DIAGRAM PER 215.5 | | | | 2) NEED TO SUBMIT PANEL SCHEDULE(S) | | | | 3) NEED TO COMPLY WITH THE ENERGY CODE FOR LIGHTING | | CONTROL AND RECEPTACLE CONTROL | | | | 4) NEED TO SUBMIT A LOAD CALCULATION PER ARTICLE 220 OF | | THE NEC. |
|