2019-08-09 07:22:45 | 8/9/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1) PERMIT APPLICATION AND INVOICE DO NOT MATCH AND ARE |
| DIFFERENT CONTRACTORS. (ROYAL ROOTER, HARRY BARBER |
| PLUMBING) |
| |
| 2) PLUMBING REPAIR TUNNEL WORK |
| A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE |
| SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO |
| EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED, |
| THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO |
| EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS. |
| DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED |
| THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE |
| CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND |
| BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW |
| GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL, |
| SECTION 318 AND THE FLORIDA BUILDING CODE, BUILDING, |
| SECTION 2603.9. |
| A SIGNED AND SEALED LETTER FROM AN ENGINEER MAY BE |
| REQUIRED TO CERTIFY THE STRUCTURAL INTEGRITY OF THE |
| EXISTING SLAB. |
| THE AREA ABOVE GRADE WHERE THE TUNNEL WAS DUG SHALL BE |
| TREATED FOR TERMITES PER THE FBC-BUILDING SEC.1816.1 OR |
| FBC-RESIDENTIAL SEC. R318. A TERMITE CERTIFICATE SHALL |
| BE ONSITE FOR FINAL INSPECTION. |
| |
| |
| |
| |
| |
| |