Plan Review Notes
Plan Review Notes For Permit 19080361
Permit Number 19080361
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-09 07:22:458/9/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) PERMIT APPLICATION AND INVOICE DO NOT MATCH AND ARE
 DIFFERENT CONTRACTORS. (ROYAL ROOTER, HARRY BARBER
 PLUMBING)
  
 2) PLUMBING REPAIR TUNNEL WORK
 A CLEAR AND LEGIBLE SANITARY RISER DIAGRAM SHALL BE
 SUBMITTED SHOWING ALL PIPE SIZES, CONNECTION POINTS TO
 EXISTING PIPING, HOW THE NEW PIPE WILL BE SUPPORTED,
 THE TYPE OF ADAPTERS USED FOR THE CONNECTIONS TO
 EXISTING PIPE, AND THE LOCATIONS OF REQUIRED CLEANOUTS.
 DETAILS AND BACKFILLING PROCEDURES SHALL BE SUBMITTED
 THAT CLEARLY SHOW HOW THE STRUCTURAL INTEGRITY OF THE
 CONCRETE SLAB WILL BE MAINTAINED DURING EXCAVATION AND
 BACKFILLING. STRUCTURAL FOAM IS NOT PERMITTED BELOW
 GROUND PER THE FLORIDA BUILDING CODE, RESIDENTIAL,
 SECTION 318 AND THE FLORIDA BUILDING CODE, BUILDING,
 SECTION 2603.9.
 A SIGNED AND SEALED LETTER FROM AN ENGINEER MAY BE
 REQUIRED TO CERTIFY THE STRUCTURAL INTEGRITY OF THE
 EXISTING SLAB.
 THE AREA ABOVE GRADE WHERE THE TUNNEL WAS DUG SHALL BE
 TREATED FOR TERMITES PER THE FBC-BUILDING SEC.1816.1 OR
 FBC-RESIDENTIAL SEC. R318. A TERMITE CERTIFICATE SHALL
 BE ONSITE FOR FINAL INSPECTION.
  
  
  
  
  
  
 ATELYO BELISLE
 PLUMBING INSPECTOR /
 PLUMBING PLANS EXAMINER
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6695
  