Plan Review Notes
Plan Review Notes For Permit 19080303
Permit Number 19080303
Review Stop G
Sequence Number 1
Notes
Date Text
2019-08-08 16:32:3708/08/2019 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1) CITY RECORDS SHOW AN EXISTING GAS RANGE AND ALSO A
 WATER HEATER ON THE GAS SYSTEM WITH A GAS. THE BTU LOAD
 OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN
 A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO
 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE
 EXISTING APPLIANCES, 2017 FBC FG SEC R2412.4, R2412.8,
 R2413.1, R2413.2, R2413.3.
 2) SUBMIT A HAND DRAWN FLOOR PLAN SHOWING THE LOCATION
 OF THE BBQ GRILL. IF THE GRILL IS LOCATED UNDER A
 ROOFED STRUCTURE, A HOOD WILL BE REQUIRED OVER THE BBQ
 GRILL, IF SO PLEASE PROVIDE MANUFACTURES RECOMMENDATION
 FOR A VENTILATION HOOD, 2017 FBC FG SEC. R2408.1
 3) SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL. FG
 SEC.305.1, FBC FG SEC. R2408.1.
 4) PLEASE SHOW SHUTOFF VALVE ON GAS ISOMERIC, 2017 FBC
 FG SEC. R2415, APPLIANCE CONNECTION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved