Plan Review Notes
Plan Review Notes For Permit 19080288
Permit Number 19080288
Review Stop B
Sequence Number 3
Notes
Date Text
2020-11-04 10:24:46PLAN REVIEW / BUILDING
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER BUILDING - PX3169
 PLANS EXAMINER 1&2 FAMILY - SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CODES IN EFFECT:
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
 NEC 2014
  
 3RD REVIEW
  
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED
 SATISFACTORILY ARE MARKED AS CORRECTED.
 PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED
 SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN
 PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER
 PREVIOUS COMMENTS.
  
 2ND REVIEW COMMENTS:
  
 ADDITION AND GUEST HOUSE 19080288 AND 19090434
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
  
 CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107
 1) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE ROOFING SYSTEMS TO BE USED.
 (NOT ADDRESSED)
 2) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVAL FOR THE MULL BAR FOR THE CONNECTION OF
 THE 2 WINDOWS MARKED "W4" MASTER BEDROOM. (NOT
 ADDRESSED)
 3) PLEASE SHOW THE WALL AND CEILING INSULATION "R"
 VALUE AND INSULATION TYPE TO MATCH THE ENERGY CALCS.
 (ENERGY CALCS NOT YET PROVIDED). CORRECTED
 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE SLIDING GLASS DOORS AND
 EXTERIOR SWING DOORS ( DOCUMENTS PROVIDED FOR THE
 EXTERIOR SWING DOOR IS NOT A COMPLETE MIAMI DADE OR
 FLORIDA STATE PRODUCT APPROVAL) (NOT ADDRESSED)
 5) DRAWING A2 - PLEASE CHECK THE WINDOW AND DOOR
 SCHEDULE - MARKS W4, W7 AND D1 DO NOT MATCH THE FLOOR
 PLAN. CORRECTED
 6) GUEST HOUSE EGRESS DOOR WIDTH AT 32 INCHES IS NOT A
 WIDE ENOUGH OPENING - WIDTH NEEDS TO COMPLY WITH FBC
 R311.2 EGRESS DOOR. CORRECTED
 NOT LESS THAN ONE EGRESS DOOR SHALL BE PROVIDED FOR
 EACH DWELLING UNIT. THE EGRESS DOOR SHALL BE
 SIDE-HINGED, AND SHALL PROVIDE A CLEAR WIDTH OF NOT
 LESS THAN 32 INCHES (813 MM) WHERE MEASURED BETWEEN THE
 FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90
 DEGREES.
  