Date |
Text |
2020-11-04 10:24:46 | PLAN REVIEW / BUILDING |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER BUILDING - PX3169 |
| PLANS EXAMINER 1&2 FAMILY - SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| NEC 2014 |
| |
| 3RD REVIEW |
| |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. |
| PREVIOUS COMMENTS THAT HAVE NOT BEEN ADDRESSED |
| SATISFACTORILY MAY HAVE ADDITIONAL COMMENTS IN |
| PARENTHESES. ANY NEW COMMENT WILL BE LISTED AFTER |
| PREVIOUS COMMENTS. |
| |
| 2ND REVIEW COMMENTS: |
| |
| ADDITION AND GUEST HOUSE 19080288 AND 19090434 |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| |
| CORRECTIONS NEEDED - FBC WPB AMENDMENTS 107 |
| 1) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE ROOFING SYSTEMS TO BE USED. |
| (NOT ADDRESSED) |
| 2) PLEASE PROVIDE THE MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVAL FOR THE MULL BAR FOR THE CONNECTION OF |
| THE 2 WINDOWS MARKED "W4" MASTER BEDROOM. (NOT |
| ADDRESSED) |
| 3) PLEASE SHOW THE WALL AND CEILING INSULATION "R" |
| VALUE AND INSULATION TYPE TO MATCH THE ENERGY CALCS. |
| (ENERGY CALCS NOT YET PROVIDED). CORRECTED |
| 4) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE |
| INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE |
| PRODUCT APPROVALS FOR THE SLIDING GLASS DOORS AND |
| EXTERIOR SWING DOORS ( DOCUMENTS PROVIDED FOR THE |
| EXTERIOR SWING DOOR IS NOT A COMPLETE MIAMI DADE OR |
| FLORIDA STATE PRODUCT APPROVAL) (NOT ADDRESSED) |
| 5) DRAWING A2 - PLEASE CHECK THE WINDOW AND DOOR |
| SCHEDULE - MARKS W4, W7 AND D1 DO NOT MATCH THE FLOOR |
| PLAN. CORRECTED |
| 6) GUEST HOUSE EGRESS DOOR WIDTH AT 32 INCHES IS NOT A |
| WIDE ENOUGH OPENING - WIDTH NEEDS TO COMPLY WITH FBC |
| R311.2 EGRESS DOOR. CORRECTED |
| NOT LESS THAN ONE EGRESS DOOR SHALL BE PROVIDED FOR |
| EACH DWELLING UNIT. THE EGRESS DOOR SHALL BE |
| SIDE-HINGED, AND SHALL PROVIDE A CLEAR WIDTH OF NOT |
| LESS THAN 32 INCHES (813 MM) WHERE MEASURED BETWEEN THE |
| FACE OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| DEGREES. |
| |