Plan Review Notes
Plan Review Notes For Permit 19080089
Permit Number 19080089
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-06 13:41:42THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET A 3 - THERE ARE NO INDICATIONS OF REVIEW AND
 COMPLIANCE WITH NFPA 150, FIRE AND LIFE SAFETY IN
 ANIMAL HOUSING FACILITIES
  
 PLEASE REVIEW AND PROVIDE AN APPLICABLE NOTE OF
 COMPLIANCE.
  
  
  
  
 2) SHEET A 1 - THERE APPEARS TO BE AN OPENING OF THE
 REAR WALL BETWEEN THE BATHROOMS AND NEW LAUNDRY ROOM
 THAT SHOWS NO DETAIL.
  
 IS THIS AN EXTERIOR WALL PORTION THAT NEEDS TO REMOVED
 AND FINISHED?
  
 PLEASE PROVIDE DETAILS.
  
  
  
 3) SHEET A 1 - THERE APPEARS TO BE NEW WALLS ALONG A
 PORTION OF THE BIG DOG ROOM/LAUNDRY ROOM SEPARATION
 THAT ARE INDICATED AS EXISTING WALLS.
  
 PLEASE REVIEW AND CORRECT OR CLARIFY.
  
  
  
 4) SHEET A 3 & E 1 - THE ARE NO EXIT SIGNS AT THE EXIT
 DISCHARGE OR EXIT PATH PER THE LIFE SAFETY PLAN.
  
 PER NFPA 101, CH 7 MEANS OF EGRESS
  
 7.10 MARKING OF MEANS OF EGRESS.
 7.10.1 GENERAL.
 7.10.1.1 WHERE REQUIRED. MEANS OF EGRESS SHALL BE
 MARKED IN
 ACCORDANCE WITH SECTION 7.10 WHERE REQUIRED IN CHAPTERS
 11
 THROUGH 43.
 7.10.1.2 EXITS.
 7.10.1.2.1* EXITS, OTHER THAN MAIN EXTERIOR EXIT DOORS
 THAT OBVIOUSLY
 AND CLEARLY ARE IDENTIFIABLE AS EXITS, SHALL BE MARKED
 BY AN APPROVED
 SIGN THAT IS READILY VISIBLE FROM ANY DIRECTION OF EXIT
 ACCESS.
  
 PLEASE REVIEW AND PROVIDE EXIT SIGNS WHERE REQUIRED.
  
  
  
 5) SHEET A 1 - THERE APPEARS TO BE WINDOWS THAT ARE
 BEING FILLED IN HOWEVER, THERE IS NO DETAIL ON THE
 IN-FILL, INCLUDING INTERIOR FINISH TYPE.
  
 PER NFPA 101, CH 38, NEW BUSINESS
  
 38.3.3 INTERIOR FINISH.
 38.3.3.1 GENERAL. INTERIOR FINISH SHALL BE IN
 ACCORDANCE WITH
 SECTION 10.2.
 38.3.3.2 INTERIOR WALL AND CEILING FINISH.
 38.3.3.2.1 INTERIOR WALL AND CEILING FINISH MATERIAL
 COMPLYING WITH
 SECTION 10.2 SHALL BE CLASS A OR CLASS B IN EXITS AND
 IN EXIT ACCESS
 CORRIDORS.
  
 PLEASE REVIEW AND PROVIDE DETAILS
  
  
  
 6) SHEET A 3 - THE NEW ADDITIONS DOES NOT INDICATED TWO
 EXITS OUT OF EACH AREA.
  
 PER NFPA 150
  
 8.1.2.1 NUMBER OF MEANS OF EGRESS.
 8.1.2.1.1 TWO MEANS OF EGRESS FOR HUMAN AND ANIMAL
 OCCUPANTS,
 AS A MINIMUM, SHALL BE PROVIDED IN EVERY FACILITY,
 SECTION,
 AND AREA WHERE SIZE, OCCUPANCY, AND ARRANGEMENT
 ENDANGER
 OCCUPANTS ATTEMPTING TO USE A SINGLE MEANS OF EGRESS
 THAT IS BLOCKED BY FIRE OR SMOKE.
 8.1.2.1.2 WHERE TWO MEANS OF EGRESS ARE REQUIRED, THEY
 SHALL
 BE ARRANGED TO MINIMIZE THE POSSIBILITY THAT BOTH MIGHT
 BE
 RENDERED IMPASSABLE BY THE SAME EMERGENCY CONDITION.
  
 PLEASE REVIEW AND INDICATED TWO EXITS AND ROUTES FROM
 EACH AREA.
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  