2019-09-10 08:58:242017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19090089
 ADD: 1022 CLEARWATER PARK
 CONT: MASTER CONTRACTORS
 TEL: 561-248-5498
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 10/2019
 ACTION: DENIED
  
 1) SHEET COVERSHEET:
 1A) OCCUPANT LOADS BUSINESS OCCUPANCY IS STATED AT 20
 SQ. FT. PLEASE REVIEW 2017 FBC-B TABLE 1004.1.2
 BUSINESS OCCUPANCY OCCUPANT LOAD FACTOR IS 100 SQ. FT.
 PER OCCUPANT. BUSINESS AREA 4347/ 100= 44 OCCUPANTS.
  
 1B) OCCUPANT LOADS STORAGE OCCUPANCY IS STATED AT 300
 SQ. FT. THIS IS CORRECT. PLEASE REVIEW 2015 FBC-B
 COMMENTARY THAT THERE CANNOT BE FRACTIONAL PARTS OF AN
 OCCUPANT YOU ALWAYS ROUND UP TO THE NEXT WHOLE NUMBER.
 ALSO SEE BOAF INFORMAL INTERPRETATION ON LINE.
  
 1C) OCCUPANT LOADS. THE BUSINESS OCCUPANCY AS STATED
 218 PLUS THE 1 OCCUPANT FROM THE STORAGE OCCUPANCY IS
 219 OCCUPANTS. HOW DO YOU COME UP WITH 230 OCCUPANTS?
 107.2.1.2 ADDITIONAL INFORMATION IS REQUIRED. TOTAL
 OCCUPANTS 44 +1 = 45 TOTAL OCCUPANTS.
  
 1D) THE SQUARE FOOT AREAS OF THE EXISTING BUILDINGS
 DOES NOT TOTAL THE GROSS SQUARE FOOT AREA GIVEN BY
 DEFINITION. FLOOR AREA, GROSS. THE FLOOR AREA OF A
 BUILDING, OR PORTION THEREOF, NOT PROVIDED WITH
 SURROUNDING EXTERIOR WALLS SHALL BE THE USABLE AREA
 UNDER THE HORIZONTAL PROJECTION OF THE ROOF OR FLOOR
 ABOVE. THE GROSS FLOOR AREA SHALL NOT INCLUDE SHAFTS
 WITH NO OPENINGS OR INTERIOR COURTS. IT WOULD APPEAR
 THE AREA BETWEEN BUILDINGS 1-2 AND BUILDING 3 THE AREA
 6.25 FT. X 75.5 = 471.875 SQ. FT. IS NOT BEING INCLUDED
 IN THE AREA CALCULATION FOR FLOOR AREA GROSS. THEN ADD
 THE ADDITIONAL SQ. FEET OF THE ADDITION995 SQ. FT.
  
 1E) DISCREPANCY IN PLANS. DEPENDING ON WHICH PAGE IN
 THE PLANS YOU GET A DIFFERENT SQUARE FOOT NUMBER FOR
 THE ADDITION. ADDITIONAL INFORMATION IS REQUIRED
 107.2.1.2. PLEASE CORRECT THE SQUARE FOOTAGE OF THE
 ADDITION.
 COVERSHEET FLOORPLAN THE ADDITION IS---------995 SQ.
 FT.
 SHEET SP-2 BUILDING 3 ADDITION CALCS. IS------985 SQ.
 FT.
 SHEET A-1 BUILDING 3 ADDITION IS---------------985 SQ.
 FT.
 SHEET M-1 BUILDING 3 ADDITION IS LISTED AS--795 SQ. FT.
  
 1F) UNDER THE HEADING CALCULATION OF WORK THE PLANS
 STATE A LEVEL III ALTERATION. PLEASE REVIEW THE 2017
 EXISTING BUILDING CODE CLASSIFICATION OF WORK SECTION
 507. 507.1 SCOPE. PROVISIONS FOR ADDITIONS SHALL APPLY
 WHERE WORK IS CLASSIFIED AS AN ADDITION AS DEFINED IN
 CHAPTER 2. ADDITION. AN EXTENSION OR INCREASE IN FLOOR
 AREA, NUMBER OF STORIES, OR HEIGHT OF A BUILDING OR
 STRUCTURE. ADDITIONS ARE FOUND IN CHAPTER 11 OF THE
 2017 EXISTING BUILDING CODE. NOT LEVEL III.
  
 2) SHEET A-1, A-3 & A-4 THE WALL PLAN LEGEND INDICATES
 THE NEW INTERIOR WALLS OF THE ADDITION SOME ARE
 INDICATED AS NEW AND SOME AS EXISTING AS WELL AS IN THE
 EXISTING BUILDING THE WALL DESIGNATION TYPE IS
 INDICATED AS ALL NEW WALLS? THE CITY FILE NET FOR
 RECORD RETENTION SHOWS PERMIT 15060795 FOR THIS SAME
 BUILDING AND THE WALL LOCATION UNDER THAT PERMIT ARE IN
 THE SAME LOCATION. 107.2.1.2 ADDITIONAL INFORMATION IS
 REQUIRED.
  
 3) SHEET A-2 NOTE ON THE PLAN EAST ELEVATION THAT
 INDICATES THE USE OF NEW JOIST HANGER TO BE SIMPSON SEE
 A-4. SHEET A-4 DOES NOT SHOW THE USE OF ANY JOIST
 HANGER. SHEET A-5 DOES SHOW THE NEW ROOF FRAMING
 MEMBERS TO BE PRESSURE TREATED 2X10 YELLOW PINE. DETAIL
 1 OF SHEET A-5 SHOWS THE 2X10 NOT IN A HANGER BUT
 SITTING ON TOP OF THE EXISTING CONCRETE BEAM.
 DISCREPANCY IN PLANS. 107.2.1.2 ADDITIONAL INFORMATION
 IS REQUIRED.
  
 4) SHEET A-5 DETAIL 1 INDICATES THE USE OF P. T. 2X10
 RAFTERS. AS DEPICTED THEY ARE DRAWN IN THE SAME SIZE AS
 THE 2X4 BOTTOM CHORD OF THE TRUSSES. THE ROOF LINE WILL
 INTERSECT FURTHER UP THE TRUSS LINE WHEN DRAWN AS A
 2X10. PLEASE NOTE THE EXISTING CONCRETE BEAM SHEET A-2
 INDICATES THE BEAM ELEVATION AT 8 FEET ABOVE FINISH
 FLOOR. DETAIL 1 SHEET A-5 ALSO SHOWS THE FURTHEST WALL
 FROM THE EXISTING BUILDING (WALL THE RAFTERS SIT ON AT
 8 FEET ELEVATION ABOVE FINISH FLOOR OR NO SLOPE ON THE
 RAFTERS. THE DESIGNER OF RECORD HAS SUBMITTED GAF
 RUBEROID MODIFIED BITUMEN ROOFING SYSTEM NOA
 18-0919.12. PLEASE NOTE UNDER THE 2017 FBC-B SECTION
 1507.11.1 THE SLOPE SHALL BE 2-PERCENT SLOPE OR NOT
 LESS THAN ? UNIT VERTICAL IN 12 UNITS HORIZONTAL OR A 4
 INCH DIFFERENCE IN HEIGHT MINIMUM.
  
 5) SHEET A-5 DETAILS 1 & 2 SHOW P. T. 2X10 RAFTERS AT 2
 FEET ON CENTER. SHEET A-5 DOES NOT GIVE US THE LIVE AND
 DEAD LOADS NOR THE GRADE OF WOOD NOR THE BENDING DESIGN
 VALUES FB. PLEASE NOTE ON THE SHEET A-0 THERE ARE NO
 DESIGN VALUES FOR DIMENSIONAL 2X10S. THERE ARE DESIGN
 VALUES FOR TRUSSES OF 30 PSF ROOF LIVE LOAD AND 25 PSF
 FOR SUPERIMPOSED DEAD LOADS. WITHIN THE FBC-B THE
 TABLES 2308.7.2(2) THE DEAD LOAD STOPS AT 20 PSF AND
 DEFLECTION OF 240. THE SAME HOLDS TRUE FOR SPAN TABLES
 FOR JOIST AND RAFTERS FROM THE AMERICAN WOOD COUNCIL
 TABLE R-10. PLEASE PROVIDE ADDITIONAL INFORMATION FOR
 GRADE OF WOOD TO BE USED AND DEAD LOAD AND DEFLECTION
 TO BE ABLE TO DETERMINE THE TIMBER SIZE.
  
 6) SHEET A-5 DETAIL # 2 INDICATES THE FINISH FLOOR
 LEVEL BUT DOES NOT PROVIDE WHAT FINISH GRADE WILL BE?
 DETAIL # 1 ON THE SAME SHEET DOES SHOW GRADE 6 INCHES
 LOWER THAN FINISH FLOOR. THERE ARE 2 AREAS OF CONCERN:
 6A) THAT THE FOUNDATION SHALL COMPLY WITH 2017 FBC-B
 SECTION 1809.4. THE MINIMUM DEPTH OF THE FOUNDATION
 BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12
 INCHES.
  
 6B) THE SECOND ISSUE FOUND IS THE NOT KNOWING WHERE THE
 FINISH GRADE IS AND THE USE OF STUCCO AND WOOD
 SUB-SHEATHING POSSIBLY AT GRADE. 2017 FBC-B SECTION
 2304.12.1.5. BETWEEN GRADE AND WOOD SIDING AND OR WOOD
 SUB-SHEATHING ON THE EXTERIOR OF THE BUILDING SHALL NOT
 BE LESS THAN 6 INCHES UNLESS THE WALL SHEATHING IS
 NATURALLY DURABLE WOOD OR PRESSURE TREATED WOOD.
  
 7) SHEET A-0 DOES NOT REQUIRE A SOILS TEST, PLEASE SHOW
 COMPLIANCE WITH 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL.
 WHERE THE CLASSIFICATION, STRENGTH OR COMPRESSIBILITY
 OF THE SOIL IS IN DOUBT OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 8) SHEET A-5 SHOWS DETAIL 1 & 2 OF THE EXISTING ROOF
 AND THE TIE-IN OF THE NEW ADDITION AND ROOF LINE. THE
 PLANS ARE SILENT AS TO HOW VENTILATION FOR ATTICS WILL
 BE ACHIEVED? PLEASE SHOW COMPLIANCE WITH THE 2017 FBC-B
 SECTION 1203.2.
  
 9) THIS REVIEW THERE WERE NO DOCUMENTS SUBMITTED FOR
 ENERGY COMPLIANCE. PLEAS SHOW HOW COMPLIANCE WITH THE
 2017 ENERGY CODE WILL BE ACHIEVED.
 C401.2 APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
  
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
  
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
  
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
 C101.5 COMPLIANCE.
  
 COMMERCIAL BUILDINGS SHALL MEET THE PROVISIONS OF
 FLORIDA BUILDING CODE, ENERGY CONSERVATION?COMMERCIAL
 PROVISIONS.
  
 C101.5.1 COMPLIANCE MATERIALS. THE FLORIDA BUILDING
 COMMISSION SHALL APPROVE SPECIFIC COMPUTER SOFTWARE.
 THE CODE OFFICIAL SHALL BE PERMITTED TO APPROVE
 WORKSHEETS, COMPLIANCE MANUALS AND OTHER SIMILAR
 MATERIALS THAT MEET THE INTENT OF THIS CODE.
  
  
 10) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  