Plan Review Notes
Plan Review Notes For Permit 19080023
Permit Number 19080023
Review Stop G
Sequence Number 2
Notes
Date Text
2019-09-16 13:17:5409/16/2019 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
 1. THE SECOND REQUEST, THIS COPY FOR THE TIE-DOWN OF
 SIGNATURE OR SEAL IS NOT IN ACCORDANCE WITH FLORIDA
 ADMINISTRATIVE CODE PER 61G15-23.001, FLORIDA STATUTE
 471. THE PROVIDED DOCUMENT FOR YOUR TIE-DOWN HAS SEAL
 AND SIGNATURE IS A COPY SIGNATURE AND NOT AN ORIGINAL
 WET STAMP.
  
 2. THE METHOD OF REQUIRED PROTECTION FOR THE LP TANK
 AND APPURTENANCES PER NFPA 58 IS MISSING INFORMATION.
 THE DETAIL ONLY SHOWS A COVER AND MUST SUBMIT A BASE
 AND COVER FOR VEHICLE TRAFFIC PROTECTION AS IT IS BELOW
 GROUND IT SHALL BE CONSTRUCTED AND PROTECTED PER NFPA
 58 SEC.3-2.2.7 (H). THE HOUSING FOR THE LID IS ALSO
 REQUIRED PER THE WPB AMENDMENTS TO THE FBC SEC. 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 3. CLEARLY INDICATE ON THE TIE-DOWN SHEET IF THE LP
 TANK TIE-DOWN METHOD AND IF YOU ARE USING FLAT STRAPS
 OR ISOLATION CABLES, IF ISOLATION CABLES, PLEASE
 CLARIFY HOW IS IT PROTECTED FOR THE LP TANK AND
 APPURTENANCES PER THE NFPA 58. WPB AMENDMENTS TO THE
 FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 4. THE DOCUMENT SUBMITTED ARE NOT TO CODE COMPLIANCE
 AND CONTINUE TO HAVE NO SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE, AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES, AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL. PLEASE MAKE AN APPOINTMENT TO DISCUSS THESE
 ITEMS THAT SHALL CONTAIN INFORMATION, IN THE FORM OF
 NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES PER THE WPB AMENDMENTS TO FBC SEC.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  