Plan Review Notes
Plan Review Notes For Permit 19071618
Permit Number 19071618
Review Stop G
Sequence Number 2
Notes
Date Text
2019-10-11 17:24:2210/11/19 2ND GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 2019 FLORIDA STATUTES
 TITLE XXXIII REGULATION OF TRADE, COMMERCE,
 INVESTMENTS, AND SOLICITATIONS
 CHAPTER 553 BUILDING CONSTRUCTION STANDARDS
 SECTION 80 ENFORCEMENT.
  
 553.80 ENFORCEMENT. (B) WITH RESPECT TO EVALUATION OF
 DESIGN PROFESSIONALS' DOCUMENTS, IF A LOCAL GOVERNMENT
 FINDS IT NECESSARY, IN ORDER TO ENFORCE COMPLIANCE WITH
 THE FLORIDA BUILDING CODE AND ISSUE A PERMIT, TO REJECT
 DESIGN DOCUMENTS REQUIRED BY THE CODE THREE OR MORE
 TIMES FOR FAILURE TO CORRECT A CODE VIOLATION
 SPECIFICALLY AND CONTINUOUSLY NOTED IN EACH REJECTION,
 INCLUDING, BUT NOT LIMITED TO, EGRESS, FIRE PROTECTION,
 STRUCTURAL STABILITY, ENERGY, ACCESSIBILITY, LIGHTING,
 VENTILATION, ELECTRICAL, MECHANICAL, PLUMBING, AND GAS
 SYSTEMS, OR OTHER REQUIREMENTS IDENTIFIED BY RULE OF
 THE FLORIDA BUILDING COMMISSION ADOPTED PURSUANT TO
 CHAPTER 120, THE LOCAL GOVERNMENT SHALL IMPOSE, EACH
 TIME AFTER THE THIRD SUCH REVIEW THE PLANS ARE REJECTED
 FOR THAT CODE VIOLATION, A FEE OF FOUR TIMES THE AMOUNT
 OF THE PROPORTION OF THE PERMIT FEE ATTRIBUTED TO PLANS
 REVIEW.
  
 THERE SEEM TO BE A GAS PERMIT THIS IS YOU SECOND REVIEW
 AND FOR IT NOT TO GO TO THIRD PLEASE CONTACT ME OR SOME
 IN OUR OFFICE TO SEE IF WE CAN CORRECT THE FOLLOWING
 ITEMS;
  
 1. UNDER THE AMENDMENTS TO THE FLORIDA BUILDING CODE,
 6TH EDITION (2017), CHAPTER 1, ADMINISTRATION OF THE
 CITY WEST PALM BEACH SECTION 107.3.5.3 RESIDENTIAL ITEM
 13 (ONE AND TWO-FAMILY). PLEASE SUBMIT AN GAS ISOMETRIC
 DRAWING THAT CLEARLY SHOWS THE LENGTH OF ALL CUT
 SECTIONS OF PIPE, WHERE YOUR METER IS LOCATED, HOW FAR
 THE DISTANCE, IS IT A 2LBS OR .05 LBS SYSTEM, LIST THE
 BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU LOAD ON
 THE SYSTEM, SHOWER UNION AND REGULATOR PER 2017 FBC
 FUEL GAS RES SECS. G2413.4.1, G2413.4.2.
  
 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS
 PER THE 2017 FBC FUEL GAS RES. SEC. G2420.4.
  
 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS
 METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE
 BUILDING AND/OR SYSTEM, LISTED SHUTOFF VALVES PER THE
 2017 FBC FUEL GAS RES. SEC. G2413.4.1.
  
 4. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES
 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 5. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC
 FUEL GAS RES. SEC. G2421.1.
  
 6. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED,
 INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE
 AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM
 THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR
 EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5.
  
 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3.
  
 8. THERE IS A FIRE PIT, SECOND TANKLESS AND POOL
 HEATER ON THE LAYOUT SUBMITTED AND NO SPECIFICATIONS OR
 INSTALLATION INSTRUCTION. AS NOTED IN ITEM 4 THERE IS A
 GAS METER ON THE MAIN HOUSE AND PERMIT 18090327 SHOW A
 RANGE, OUTDOOR GRILL AND 199 BTU?S TANKLESS WHICH IS
 NOT ADDED TO THE SYSTEM, PLEASE CLARIFY AND MAKE
 CORRECTION PER THE WPB AMENDMENTS TO THE FBC SEC.
 105.1.
  
 9. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE
 OF IGNITION IF NOT THERE AT TIME OF INSTALLATION, WPB
 AMENDMENTS TO THE FBC SEC. 105.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  