2019-08-06 06:55:03 | 08/06/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. 1. SUBMIT AN GAS ISOMETRIC DRAWING THAT CLEARLY |
| SHOWS THE LENGTH OF ALL CUT SECTIONS OF PIPE, WHERE |
| YOUR METER IS LOCATED, HOW FAR THE DISTANCE, IS IT A |
| 2LBS OR .05LBS SYSTEM, LIST THE BTU LOAD OF EACH |
| APPLIANCE AND THE TOTAL BTU LOAD ON THE SYSTEM, SHOWER |
| UNION AND REGULATOR PER 2017 FBC FUEL GAS RES SECS. |
| G2413.4.1, G2413.4.2. |
| 2. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS. |
| A 2017 FBC FUEL GAS RES. SEC. G2420.4. |
| 3. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, (GAS |
| METER / MP REGULATOR) TO THE MOST REMOTE OUTLET IN THE |
| BUILDING AND/OR SYSTEM, LISTED SHUTOFF VALVES PER THE |
| 2017 FBC FUEL GAS RES. SEC. G2413.4.1. |
| 4. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES |
| 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1, |
| G2413.2, G2413.3. |
| 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 6. REGULATORS INSTALLED OUTDOORS SHALL BE DESIGNED, |
| INSTALLED OR PROTECTED SO THEIR OPERATION WILL NOT BE |
| AFFECTED BY THE ELEMENTS. PROVIDE DOCUMENTATION FROM |
| THE MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| 7. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE |
| DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS |
| OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR |
| ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS |
| SYSTEM 2017 FBC FUEL GAS RES. SEC. G2413.3. |
| 8. ON THE HOUSE PLAN SHOW THE LOCATION OF THE TANKLESS |
| WATER HEATER AND THE LOCATION AND DISTANCE OF ANY |
| OPERABLE DOORS OR WINDOWS IN RELATION TO THE WATER |
| HEATER. THE LOCATION OF THE WATER HEATER SHALL COMPLY |
| WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| HOUSE PLAN CAN BE HAND DRAWN. WPB AMENDMENTS TO THE FBC |
| SEC. 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 9. A SUB ELECTRICAL PERMIT IS REQUIRED FOR THE SOURCE |
| OF IGNITION IF NOT THERE AT TIME OF INSTALATION, WPB |
| AMENDMENTS TO THE FBC SEC. 105.1 |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |