2019-08-02 16:42:20 | 08/02/2019 1ST PLUMBING/BACKFLOW REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. ON THE ISOMETRIC DRAWING PLEASE SHOWS THE VALVE, |
| SEDIMENT TRAP AND REGULATOR PER, 2017 FBC FUEL GAS RES |
| SECS. G2413.4.1, G2413.4.2. |
| 2. THIS UNIT REQUIRES A REGULATOR AS IT HAS 10.5? WC |
| MINIMUM AND THE METER IS 12? WC. PLEASE SUBMIT |
| MANUFACTURES SPECIFICATION FOR REGULATOR, REGULATORS |
| INSTALLED OUTDOORS SHALL BE DESIGNED, INSTALLED OR |
| PROTECTED SO THEIR OPERATION WILL NOT BE AFFECTED BY |
| THE ELEMENTS. PROVIDE DOCUMENTATION FROM THE |
| MANUFACTURER THAT THE REGULATORS ARE APPROVED FOR |
| EXTERIOR USE. NFPA 58-11 SEC. 6.8.1.5. |
| 3. THIS UNIT REQUIRES A 120 VOLT OUTLET FOR SOURCE OF |
| IGNITION AND A SUB ELECTRICAL PERMIT IS REQUIRED FOR |
| THE SOURCE OF IGNITION IF ONE NOT WITHIN RANGE, WPB |
| AMENDMENTS TO THE FBC SEC. 105.1. |
| 4. THE VALUE LISTED ON THE PLUMBING APPLICATION AND THE |
| OVERALL VALUE IS LOW. PROVIDE BONA FIDE SIGNED CONTRACT |
| PER WPB AMENDMENTS TO THE FBC 109.3 BUILDING PERMITS |
| VALUATIONS. IF IN THE OPINION OF THE BUILDING OFFICIAL, |
| THE CLAIMED VALUATION OF BUILDING, ALTERATION, |
| STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR PLUMBING |
| SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| APPLICATION, THE PERMIT SHALL BE DENIED UNLESS THE |
| APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |