2019-08-09 13:14:43THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) A 20' FIRE LANE OPENING IS REQUIRED.
  
 PER NFPA 1, CH 18
  
 18.2.3.4 SPECIFICATIONS.
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (6.1 M).
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 2) A KNOX PADLOCK IS RECOMMENDED FOR FD EMERGENCY
 INCIDENT ACCESS. THE LOCK CAN BE USED IN CONJUNCTION
 WITH YOUR PADLOCK.
  
  