Plan Review Notes For Permit 19071602 |
Permit Number |
19071602 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-09 13:14:43 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, | | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | PLEASE CONSIDER THE FOLLOWING AS PROVISO: | | | | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED | | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE | | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE | | INSPECTION. | | | | | | 1) A 20' FIRE LANE OPENING IS REQUIRED. | | | | PER NFPA 1, CH 18 | | | | 18.2.3.4 SPECIFICATIONS. | | 18.2.3.4.1 DIMENSIONS. | | 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN | | UNOBSTRUCTED | | WIDTH OF NOT LESS THAN 20 FT (6.1 M). | | | | PLEASE ENSURE COMPLIANCE. | | | | | | | | 2) A KNOX PADLOCK IS RECOMMENDED FOR FD EMERGENCY | | INCIDENT ACCESS. THE LOCK CAN BE USED IN CONJUNCTION | | WITH YOUR PADLOCK. | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|