2019-08-05 14:28:11 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19071544 |
| ADD: 777 S FLAGLER DR. 19TH FLOOR |
| CONT: BUTLER CONSTRUCTION |
| TEL: 561-832-9700 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. AUGUST 05/2019 |
| ACTION: DENIED |
| |
| 1) ASBESTOS: IN ACCORDANCE WITH SECTION 553.79 F. S. |
| THIS IS TO ADVISE YOU OF THE OWNERS OR OPERATORS? |
| RESPONSIBILITY TO COMPLY WITH THE STATE & FEDERAL |
| ASBESTOS REGULATIONS, INCLUDING SECTION 376.60 F. S. |
| AND CFR 61- NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- |
| ASBESTOS SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION |
| TO THE DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: |
| * DEMOLITION OF ALL REGULATED STRUCTURES; |
| * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| |
| FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| POLLUTION CONTROL SECTION) |
| |
| 901 EVERNIA STREET |
| WEST PALM BEACH, FL 33401 |
| (561) 355-3070 |
| |
| 2) SHEET A119 19TH FLOOR DEMOLITION PLAN IT WOULD |
| APPEAR THE ELEVATOR LOBBY DOORS ARE BEING REMOVED. THE |
| SYMBOLS SHEET A001 GENERAL NOTES AND SYMBOLS DOES NOT |
| HAVE A SYMBOL FOR DOOR REMOVAL BUT A DOUBLE DASHED LINE |
| DOES REPRESENT THE REMOVAL OF WALLS. |
| 2017 EXISTING BUILDING CODE 803.2.2 SUPPLEMENTAL SHAFT |
| AND FLOOR OPENING ENCLOSURE REQUIREMENTS. |
| WHERE THE WORK AREA ON ANY FLOOR EXCEEDS 50 PERCENT OF |
| THAT FLOOR AREA, THE ENCLOSURE REQUIREMENTS OF SECTION |
| 803.2 SHALL APPLY TO VERTICAL OPENINGS OTHER THAN |
| STAIRWAYS THROUGHOUT THE FLOOR. |
| |
| 2017 FBC-B 1016.2 EGRESS THROUGH INTERVENING SPACES. |
| EGRESS THROUGH INTERVENING SPACES SHALL COMPLY WITH |
| THIS SECTION. |
| 1.EXIT ACCESS THROUGH AN ENCLOSED ELEVATOR LOBBY IS |
| PERMITTED. ACCESS TO NOT LESS THAN ONE OF THE REQUIRED |
| EXITS SHALL BE PROVIDED WITHOUT TRAVEL THROUGH THE |
| ENCLOSED ELEVATOR LOBBIES REQUIRED BY SECTION 3006. |
| WHERE THE PATH OF EXIT ACCESS TRAVEL PASSES THROUGH AN |
| ENCLOSED ELEVATOR LOBBY, THE LEVEL OF PROTECTION |
| REQUIRED FOR THE ENCLOSED ELEVATOR LOBBY IS NOT |
| REQUIRED TO BE EXTENDED TO THE EXIT UNLESS DIRECT |
| ACCESS TO AN EXIT IS REQUIRED BY OTHER SECTIONS OF THIS |
| CODE. |
| |
| 3) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |