Plan Review Notes
Plan Review Notes For Permit 19071443
Permit Number 19071443
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-08 04:18:381) SHT. 3 OF 3 SHOWS A MAIN DRAIN IN THE SPA AND THE
 PIPING SCHEMATIC SHOWS ONE BUT NOT ON THE PLAN VIEW ON
 SHT. 1. CLARIFY.
 2) SUBMIT TOTAL DYNAMIC HEAD CALCULATIONS FOR THE
 MAXIMUM SYSTEM FLOW FOR THE SPA.. THE MAXIMUM FLOW OF
 THE PUMP FROM ITS PUMP CURVE AND THE SIMPLIFIED TOTAL
 DYNAMIC HEAD CALCULATION IS NO LONGER ALLOWED TO BE
 USED IN DETERMINING MAXIMUM SYSTEM FLOW RATE PER
 ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9, 4.4.9.1. THE 2013
 EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE
 (GPM). IT REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES
 NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION
 OUTLET FITTING ASSEMBLY (DRAIN COVER).THE TDH
 CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS
 INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES,
 HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS
 EXCEPT THE PUMP.
 3) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN
 DRAINS. WPB AMEND. TO FBC SEC. 107.2.1.
 4) IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS
 SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS
 IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE
 TDH CALCULATIONS. ANSI/APSP/ICC 7 - 2013 SECS. 4.4.9,
 4.4.9.1.
 5) THE PROJECT SPECIFIC DETAILS ON SHT. 1CALL OUT A VS
 PENTAIR PUMP BUT THE SUBMITTED SPECS ARE FOR A VF PUMP.
 CLARIFY.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  