Plan Review Notes For Permit 19071425 |
Permit Number |
19071425 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-08-08 16:11:25 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 3RD BUILDING REVIEW DENIED: | | | | PLEASE NOTE THAT TEST REPORTS FOR (UNDERLAYMENT WITH | | TYPE OF FLOORING) ARE REQUIRED. | | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO | | DISCREPANCIES BETWEEN | | SPEC SHEETS, BROCHURES AND TEST REPORTS FOR SOME | | MANUFACTURERS (NOT NECESSARILY THE MANUFACTURER | | SELECTED; THIS IS A GENERAL COMMENT). | | | | FBC B 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE | | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL | | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID | | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED | | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. | | | | SEE803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E | | 84 | | OR UL 723. | | | | PLEASE FEEL FREE TO CONTACT ME WITH ANY QUESTIONS THAT | | I MAY BE ABLE TO HELP WITH. | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 |
|