Date |
Text |
2019-07-31 14:20:28 | 07/31/2018 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THE LICENSE YOUR COMPANY HOLDS IN THIS APPLICATION |
| DOES NOT ALLOW YOUR COMPANY TO INSTALL THIS BACKFLOW |
| DEVICE, PLEASE REFER TO 2012 FLORIDA STATUTES 489.103 |
| (3) (N)?UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR? |
| MEANS A CONTRACTOR WHOSE SERVICES ARE LIMITED TO THE |
| CONSTRUCTION, INSTALLATION, AND REPAIR, ON PUBLIC OR |
| PRIVATE PROPERTY, WHETHER ACCOMPLISHED THROUGH OPEN |
| EXCAVATIONS OR THROUGH OTHER MEANS, INCLUDING, BUT NOT |
| LIMITED TO, DIRECTIONAL DRILLING, AUGER BORING, JACKING |
| AND BORING, TRENCHLESS TECHNOLOGIES, WET AND DRY TAPS, |
| GROUTING, AND SLIP LINING, OF MAIN SANITARY SEWER |
| COLLECTION SYSTEMS, MAIN WATER DISTRIBUTION SYSTEMS, |
| STORM SEWER COLLECTION SYSTEMS, AND THE CONTINUATION OF |
| UTILITY LINES FROM THE MAIN SYSTEMS TO A POINT OF |
| TERMINATION UP TO AND INCLUDING THE METER LOCATION FOR |
| THE INDIVIDUAL OCCUPANCY, SEWER COLLECTION SYSTEMS AT |
| PROPERTY LINE ON RESIDENTIAL OR SINGLE-OCCUPANCY |
| COMMERCIAL PROPERTIES, OR ON MULTIOCCUPANCY PROPERTIES |
| AT MANHOLE OR WYE LATERAL EXTENDED TO AN INVERT |
| ELEVATION AS ENGINEERED TO ACCOMMODATE FUTURE BUILDING |
| SEWERS, WATER DISTRIBUTION SYSTEMS, OR STORM SEWER |
| COLLECTION SYSTEMS AT STORM SEWER STRUCTURES. HOWEVER, |
| AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY |
| INSTALL EMPTY UNDERGROUND CONDUITS IN RIGHTS-OF-WAY, |
| EASEMENTS, PLATTED RIGHTS-OF-WAY IN NEW SITE |
| DEVELOPMENT, AND SLEEVES FOR PARKING LOT CROSSINGS NO |
| SMALLER THAN 2 INCHES IN DIAMETER IF EACH CONDUIT |
| SYSTEM INSTALLED IS DESIGNED BY A LICENSED PROFESSIONAL |
| ENGINEER OR AN AUTHORIZED EMPLOYEE OF A MUNICIPALITY, |
| COUNTY, OR PUBLIC UTILITY AND THE INSTALLATION OF SUCH |
| CONDUIT DOES NOT INCLUDE INSTALLATION OF ANY CONDUCTOR |
| WIRING OR CONNECTION TO AN ENERGIZED ELECTRICAL SYSTEM. |
| AN UNDERGROUND UTILITY AND EXCAVATION CONTRACTOR MAY |
| NOT INSTALL PIPING THAT IS AN INTEGRAL PART OF A FIRE |
| PROTECTION SYSTEM AS DEFINED IN S. 633.021 BEGINNING AT |
| THE POINT WHERE THE PIPING IS USED EXCLUSIVELY FOR SUCH |
| A SYSTEM. PLEASE PROVE PROPER PAPERWORK SUPPORTING YOUR |
| LICENSE FOR THIS TYPE OF WORK. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |