2019-07-29 13:50:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THERE IS INSUFFICIENT INFORMATION PROVIDE TO |
| COMPLETE A THOROUGH LIFE SAFETY REVIEW. |
| |
| |
| |
| 2) SHEET A 201 - THERE IS NO REFERENCE OF REVIEW OR |
| COMPLIANCE WITH THE FLORIDA FIRE PREVENTION CODE. |
| |
| PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH |
| INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101; |
| SPECIFICALLY, CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES. |
| |
| PLEASE REVIEW. ENSURE COMPLIANCE AND PROVIDE THE |
| REFERENCE. |
| |
| |
| |
| 3) SHEET A 201 - THERE ARE NO AGE GROUPD INDICATED. |
| |
| PER NFPA 101, CH 14 |
| |
| 14.1.2.2 EDUCATIONAL OCCUPANCIES SHALL INCLUDE |
| PRESCHOOLS, |
| KINDERGARTENS, AND OTHER SCHOOLS MEETING BOTH OF THE |
| FOLLOWING |
| CRITERIA: |
| (1) THE PURPOSE IS PRIMARILY EDUCATIONAL, EVEN THOUGH |
| THE |
| CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL AGE. |
| (2) THE CHILDREN ARE ALL 24 MONTHS OF AGE OR OLDER. |
| |
| PLEASE PROVIDE THE AGE GROUPS. |
| |
| |
| |
| 4) THERE IS NO DOOR SCHEDULE INDICATED SHOWING LOCKS |
| AND HARDWARE. |
| |
| PER NFPA 14 |
| |
| 14.2.2.2 DOORS. |
| 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| PERMITTED. |
| 14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM |
| AN AREA |
| HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE |
| PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF |
| THE LATCH OR |
| LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING |
| WITH |
| 7.2.1.7. |
| |
| PLEASE PROVIDE DETAILS AND A DOOR SCHEDULE. |
| |
| |
| |
| 5) THE PROPOSED OCCUPANCY IS INDICATED ON THE 2ND FLLOR |
| |
| PER NFPA 14 |
| |
| 14.2 MEANS OF EGRESS REQUIREMENTS. |
| 14.2.1 GENERAL. |
| 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH |
| CHAPTER 7 |
| AND SECTION 14.2. |
| 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL, |
| KINDERGARTEN, OR |
| FIRST-GRADE STUDENTS SHALL BE LOCATED ON A LEVEL OF |
| EXIT DISCHARGE, |
| UNLESS OTHERWISE PERMITTED BY 14.2.1.4. |
| 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE |
| STUDENTS SHALL |
| NOT BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF |
| EXIT DISCHARGE, |
| UNLESS OTHERWISE PERMITTED BY 14.2.1.4. |
| 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER |
| THAN AS |
| SPECIFIED IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED |
| TO BE USED |
| WHERE PROVIDED WITH INDEPENDENT MEANS OF EGRESS |
| DEDICATED FOR |
| USE BY THE PRESCHOOL, KINDERGARTEN, FIRST-GRADE, OR |
| SECOND-GRADE |
| STUDENTS. |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| |
| |
| |
| 6) THERE ARE NO INDICATIONS OF THE CORRIDOR WIDTH. |
| |
| PER NFPA 101, CH 14 |
| |
| 14.2.3 CAPACITY OF MEANS OF EGRESS. |
| 14.2.3.1 GENERAL. CAPACITY OF MEANS OF EGRESS SHALL BE |
| IN |
| ACCORDANCE WITH SECTION 7.3. |
| 14.2.3.2 MINIMUM CORRIDOR WIDTH. EXIT ACCESS CORRIDORS |
| SHALL |
| HAVE NOT LESS THAN 6 FT (1830 MM) OF CLEAR WIDTH. |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| |
| |
| |
| 7) SHEET A 201 - THERE IS A DOOR FROM THE EXISTING |
| WAITING AREA THAT OPENS INTO THE EXIT CORRIDOR |
| |
| PER NFPA 101, CH 14 |
| |
| 14.2.5.6 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR |
| SHALL BE |
| ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL. |
| (SEE ALSO |
| 7.2.1.4.3.) |
| |
| PLEASE REVIEW AND CORRECT OF PROVIDE DETAILS IN |
| COMPLIANCE. |
| |
| |
| |
| 8) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING. |
| |
| PER NFPA 14 |
| |
| 14.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| PROVIDED IN ACCORDANCE WITH SECTION 7.9. |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE |
| |
| |
| |
| 9) THERE ARE NO INDICATIONS OF A COMPLETE FIRE ALARM |
| SYSTEM |
| |
| PER NFPA 101, CH 14 |
| |
| 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS. |
| 14.3.4.1 GENERAL. |
| 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED |
| WITH A FIRE |
| ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6. |
| 14.3.4.2 INITIATION. |
| 14.3.4.2.1 GENERAL. INITIATION OF THE REQUIRED FIRE |
| ALARM SYSTEM, |
| OTHER THAN AS PERMITTED BY 14.3.4.2.3, SHALL BE BY |
| MANUAL MEANS IN |
| ACCORDANCE WITH 9.6.2.1(1). |
| 14.3.4.2.2 AUTOMATIC INITIATION. IN BUILDINGS PROVIDED |
| WITH |
| AUTOMATIC SPRINKLER PROTECTION, THE OPERATION OF THE |
| SPRINKLER |
| SYSTEM SHALL AUTOMATICALLY ACTIVATE THE FIRE ALARM |
| SYSTEM IN |
| ADDITION TO THE INITIATION MEANS REQUIRED IN |
| 14.3.4.2.1. |
| |
| 14.3.4.3.1 OCCUPANT NOTIFICATION. |
| 14.3.4.3.1.1 OCCUPANT NOTIFICATION SHALL BE |
| ACCOMPLISHED |
| AUTOMATICALLY IN ACCORDANCE WITH 9.6.3. |
| 14.3.4.3.1.2 THE OCCUPANT NOTIFICATION REQUIRED BY |
| 14.3.4.3.1.1 |
| SHALL UTILIZE AN EMERGENCY VOICE/ALARM COMMUNICATION |
| SYSTEM IN |
| ACCORDANCE WITH 9.6.3 WHERE THE BUILDING HAS AN |
| OCCUPANT LOAD OF |
| MORE THAN 100. |
| |
| PLEASE PROVIDE DETAILS IN COMPLIANCE. |
| |
| |
| |
| |
| 10) SHEET A 201 - THERE ARE MULTIPLE CLASSROOMS THAT |
| REQUIRE EXIT THROUGH AN AJOINING ROOM OR SPACE. |
| |
| PER NFPA 101, CH 14 |
| |
| 14.2.5.5 EVERY ROOM THAT IS NORMALLY SUBJECT TO STUDENT |
| OCCUPANCY |
| SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN |
| EXIT ACCESS |
| CORRIDOR OR EXIT, UNLESS OTHERWISE PERMITTED BY ONE OF |
| THE |
| FOLLOWING: |
| (1) THIS REQUIREMENT SHALL NOT APPLY WHERE AN EXIT DOOR |
| OPENS |
| DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR BALCONY OR |
| CORRIDOR AS |
| DESCRIBED IN 14.2.5.9. |
| (2) ONE ROOM SHALL BE PERMITTED TO INTERVENE BETWEEN A |
| NORMALLY |
| OCCUPIED STUDENT ROOM AND AN EXIT ACCESS CORRIDOR, |
| PROVIDED |
| THAT ALL OF THE FOLLOWING CRITERIA ARE MET: |
| (A) THE TRAVEL FROM A ROOM SERVED BY AN INTERVENING |
| ROOM |
| TO THE CORRIDOR DOOR OR EXIT SHALL NOT EXCEED 75 FT (23 |
| M). |
| (B) CLOTHING, PERSONAL EFFECTS, OR OTHER MATERIALS |
| DEEMED |
| HAZARDOUS BY THE AUTHORITY HAVING JURISDICTION SHALL BE |
| STORED IN METAL LOCKERS, PROVIDED THAT THEY DO NOT |
| OBSTRUCT THE EXIT ACCESS, OR THE INTERVENING ROOM SHALL |
| BE |
| SPRINKLERED IN ACCORDANCE WITH SECTION 9.7. |
| (C) ONE OF THE FOLLOWING MEANS OF PROTECTION SHALL BE |
| PROVIDED: |
| I. THE INTERVENING ROOM SHALL HAVE APPROVED FIRE |
| DETECTION THAT ACTIVATES THE BUILDING ALARM. |
| II. THE BUILDING SHALL BE PROTECTED BY AN APPROVED, |
| SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| ACCORDANCE WITH SECTION 9.7. |
| |
| PLEASE REVIEW AND PROVIDE TRAVEL DISTANCES AND OTHER |
| REQUIRED DETAILS IN COMPLIANCE. |
| |
| |
| |
| 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| |
| 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |