Plan Review Notes
Plan Review Notes For Permit 19071411
Permit Number 19071411
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-29 13:50:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE IS INSUFFICIENT INFORMATION PROVIDE TO
 COMPLETE A THOROUGH LIFE SAFETY REVIEW.
  
  
  
 2) SHEET A 201 - THERE IS NO REFERENCE OF REVIEW OR
 COMPLIANCE WITH THE FLORIDA FIRE PREVENTION CODE.
  
 PROPOSED PROJECTS SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE WHICH
 INCLUDES THE 2015 EDITION OF NFPA 1 AND NFPA 101;
 SPECIFICALLY, CHAPTER 14 NEW EDUCATIONAL OCCUPANCIES.
  
 PLEASE REVIEW. ENSURE COMPLIANCE AND PROVIDE THE
 REFERENCE.
  
  
  
 3) SHEET A 201 - THERE ARE NO AGE GROUPD INDICATED.
  
 PER NFPA 101, CH 14
  
 14.1.2.2 EDUCATIONAL OCCUPANCIES SHALL INCLUDE
 PRESCHOOLS,
 KINDERGARTENS, AND OTHER SCHOOLS MEETING BOTH OF THE
 FOLLOWING
 CRITERIA:
 (1) THE PURPOSE IS PRIMARILY EDUCATIONAL, EVEN THOUGH
 THE
 CHILDREN WHO ATTEND SUCH SCHOOLS ARE OF PRESCHOOL AGE.
 (2) THE CHILDREN ARE ALL 24 MONTHS OF AGE OR OLDER.
  
 PLEASE PROVIDE THE AGE GROUPS.
  
  
  
 4) THERE IS NO DOOR SCHEDULE INDICATED SHOWING LOCKS
 AND HARDWARE.
  
 PER NFPA 14
  
 14.2.2.2 DOORS.
 14.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE
 PERMITTED.
 14.2.2.2.2 ANY DOOR IN A REQUIRED MEANS OF EGRESS FROM
 AN AREA
 HAVING AN OCCUPANT LOAD OF 100 OR MORE PERSONS SHALL BE
 PERMITTED TO BE PROVIDED WITH A LATCH OR LOCK ONLY IF
 THE LATCH OR
 LOCK IS PANIC HARDWARE OR FIRE EXIT HARDWARE COMPLYING
 WITH
 7.2.1.7.
  
 PLEASE PROVIDE DETAILS AND A DOOR SCHEDULE.
  
  
  
 5) THE PROPOSED OCCUPANCY IS INDICATED ON THE 2ND FLLOR
  
 PER NFPA 14
  
 14.2 MEANS OF EGRESS REQUIREMENTS.
 14.2.1 GENERAL.
 14.2.1.1 MEANS OF EGRESS SHALL BE IN ACCORDANCE WITH
 CHAPTER 7
 AND SECTION 14.2.
 14.2.1.2 ROOMS NORMALLY OCCUPIED BY PRESCHOOL,
 KINDERGARTEN, OR
 FIRST-GRADE STUDENTS SHALL BE LOCATED ON A LEVEL OF
 EXIT DISCHARGE,
 UNLESS OTHERWISE PERMITTED BY 14.2.1.4.
 14.2.1.3 ROOMS NORMALLY OCCUPIED BY SECOND-GRADE
 STUDENTS SHALL
 NOT BE LOCATED MORE THAN ONE STORY ABOVE A LEVEL OF
 EXIT DISCHARGE,
 UNLESS OTHERWISE PERMITTED BY 14.2.1.4.
 14.2.1.4 ROOMS OR AREAS LOCATED ON FLOOR LEVELS OTHER
 THAN AS
 SPECIFIED IN 14.2.1.2 AND 14.2.1.3 SHALL BE PERMITTED
 TO BE USED
 WHERE PROVIDED WITH INDEPENDENT MEANS OF EGRESS
 DEDICATED FOR
 USE BY THE PRESCHOOL, KINDERGARTEN, FIRST-GRADE, OR
 SECOND-GRADE
 STUDENTS.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 6) THERE ARE NO INDICATIONS OF THE CORRIDOR WIDTH.
  
 PER NFPA 101, CH 14
  
 14.2.3 CAPACITY OF MEANS OF EGRESS.
 14.2.3.1 GENERAL. CAPACITY OF MEANS OF EGRESS SHALL BE
 IN
 ACCORDANCE WITH SECTION 7.3.
 14.2.3.2 MINIMUM CORRIDOR WIDTH. EXIT ACCESS CORRIDORS
 SHALL
 HAVE NOT LESS THAN 6 FT (1830 MM) OF CLEAR WIDTH.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
 7) SHEET A 201 - THERE IS A DOOR FROM THE EXISTING
 WAITING AREA THAT OPENS INTO THE EXIT CORRIDOR
  
 PER NFPA 101, CH 14
  
 14.2.5.6 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE
 ARRANGED TO PREVENT INTERFERENCE WITH CORRIDOR TRAVEL.
 (SEE ALSO
 7.2.1.4.3.)
  
 PLEASE REVIEW AND CORRECT OF PROVIDE DETAILS IN
 COMPLIANCE.
  
  
  
 8) THERE ARE NO INDICATIONS OF EMERGENCY LIGHTING.
  
 PER NFPA 14
  
 14.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE
 PROVIDED IN ACCORDANCE WITH SECTION 7.9.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE
  
  
  
 9) THERE ARE NO INDICATIONS OF A COMPLETE FIRE ALARM
 SYSTEM
  
 PER NFPA 101, CH 14
  
 14.3.4 DETECTION, ALARM, AND COMMUNICATIONS SYSTEMS.
 14.3.4.1 GENERAL.
 14.3.4.1.1 EDUCATIONAL OCCUPANCIES SHALL BE PROVIDED
 WITH A FIRE
 ALARM SYSTEM IN ACCORDANCE WITH SECTION 9.6.
 14.3.4.2 INITIATION.
 14.3.4.2.1 GENERAL. INITIATION OF THE REQUIRED FIRE
 ALARM SYSTEM,
 OTHER THAN AS PERMITTED BY 14.3.4.2.3, SHALL BE BY
 MANUAL MEANS IN
 ACCORDANCE WITH 9.6.2.1(1).
 14.3.4.2.2 AUTOMATIC INITIATION. IN BUILDINGS PROVIDED
 WITH
 AUTOMATIC SPRINKLER PROTECTION, THE OPERATION OF THE
 SPRINKLER
 SYSTEM SHALL AUTOMATICALLY ACTIVATE THE FIRE ALARM
 SYSTEM IN
 ADDITION TO THE INITIATION MEANS REQUIRED IN
 14.3.4.2.1.
  
 14.3.4.3.1 OCCUPANT NOTIFICATION.
 14.3.4.3.1.1 OCCUPANT NOTIFICATION SHALL BE
 ACCOMPLISHED
 AUTOMATICALLY IN ACCORDANCE WITH 9.6.3.
 14.3.4.3.1.2 THE OCCUPANT NOTIFICATION REQUIRED BY
 14.3.4.3.1.1
 SHALL UTILIZE AN EMERGENCY VOICE/ALARM COMMUNICATION
 SYSTEM IN
 ACCORDANCE WITH 9.6.3 WHERE THE BUILDING HAS AN
 OCCUPANT LOAD OF
 MORE THAN 100.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE.
  
  
  
  
 10) SHEET A 201 - THERE ARE MULTIPLE CLASSROOMS THAT
 REQUIRE EXIT THROUGH AN AJOINING ROOM OR SPACE.
  
 PER NFPA 101, CH 14
  
 14.2.5.5 EVERY ROOM THAT IS NORMALLY SUBJECT TO STUDENT
 OCCUPANCY
 SHALL HAVE AN EXIT ACCESS DOOR LEADING DIRECTLY TO AN
 EXIT ACCESS
 CORRIDOR OR EXIT, UNLESS OTHERWISE PERMITTED BY ONE OF
 THE
 FOLLOWING:
 (1) THIS REQUIREMENT SHALL NOT APPLY WHERE AN EXIT DOOR
 OPENS
 DIRECTLY TO THE OUTSIDE OR TO AN EXTERIOR BALCONY OR
 CORRIDOR AS
 DESCRIBED IN 14.2.5.9.
 (2) ONE ROOM SHALL BE PERMITTED TO INTERVENE BETWEEN A
 NORMALLY
 OCCUPIED STUDENT ROOM AND AN EXIT ACCESS CORRIDOR,
 PROVIDED
 THAT ALL OF THE FOLLOWING CRITERIA ARE MET:
 (A) THE TRAVEL FROM A ROOM SERVED BY AN INTERVENING
 ROOM
 TO THE CORRIDOR DOOR OR EXIT SHALL NOT EXCEED 75 FT (23
 M).
 (B) CLOTHING, PERSONAL EFFECTS, OR OTHER MATERIALS
 DEEMED
 HAZARDOUS BY THE AUTHORITY HAVING JURISDICTION SHALL BE
 STORED IN METAL LOCKERS, PROVIDED THAT THEY DO NOT
 OBSTRUCT THE EXIT ACCESS, OR THE INTERVENING ROOM SHALL
 BE
 SPRINKLERED IN ACCORDANCE WITH SECTION 9.7.
 (C) ONE OF THE FOLLOWING MEANS OF PROTECTION SHALL BE
 PROVIDED:
 I. THE INTERVENING ROOM SHALL HAVE APPROVED FIRE
 DETECTION THAT ACTIVATES THE BUILDING ALARM.
 II. THE BUILDING SHALL BE PROTECTED BY AN APPROVED,
 SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN
 ACCORDANCE WITH SECTION 9.7.
  
 PLEASE REVIEW AND PROVIDE TRAVEL DISTANCES AND OTHER
 REQUIRED DETAILS IN COMPLIANCE.
  
  
  
 11) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
  
 12) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  