2019-08-05 13:36:53 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19071411 |
| ADD: 307 EVERNIA ST. SUITE: 200 |
| CONT: 489 EXEMPT. NO WORK/ CHANGE OF OCCUPANCY |
| TEL: 970-903-5721 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MON. AUGUST 05/ 2019 |
| ACTION: DENIED |
| |
| 1) SHEET A-201: |
| |
| 1A) DISCREPANCIES IN THE PLAN, OCCUPANT LOADS: |
| 1A)(1) ON THE LEFT SIDE OF THE PLAN THERE ARE 2 |
| CLASSROOMS WITH 265 SQ. FT. OF CLASSROOM, ONE IS LARGER |
| THAN THE OTHER AND ONE HAS 13 OCCUPANTS AND THE OTHER 6 |
| OCCUPANTS. DISCREPANCY, 107.2.1.2. ADDITIONAL |
| INFORMATION IS REQUIRED. IT APPEARS THIS MAYBE A STAFF |
| AREA WITH SINK IN A BREAK ROOM? |
| |
| 1A)(2) THE CLASSROOM ON THE RIGHT SIDE OF THE SHEET |
| INDICATES 275 SQ. FT. AND OCCUPANT LOAD OF 14. THE |
| ACTUAL OCCUPANT LOAD IS 13.75, NEED TO BE ROUNDED DOWN |
| TO THE NEXT WHOLE NUMBER SINCE THERE IS NO PARTS OF |
| OCCUPANTS. TABLE 1004.1.2. |
| |
| 1A)(3) THERE IS NO OCCUPANT LOAD GIVEN FOR THE LIBRARY |
| AT ALL. PLEASE REFER TO THE 2017 FBC-B TABLE |
| 1004.1.2. |
| |
| 1A)(4) NO OCCUPANT LOADS HAVE BEEN GIVEN TO THE |
| RECEPTION AREA, WAITING AREA NOR EXISTING STORAGE ROOM, |
| OR THE FILE/ COPY ROOM. 107.2.1.2. ADDITIONAL |
| INFORMATION IS REQUIRED. FBC-B TABLE 1004.1.2. |
| |
| 1B) THE PERMIT APPLICATION INDICATES THIS IS A CHANGE |
| IN OCCUPANCY. SHEET A-201 INDICATES THAT THIS SPACE WAS |
| USED AS A BUSINESS OCCUPANCY AND NOW IS TO BE A SCHOOL. |
| PLEASE PROVIDE THE AGE OF THE STUDENTS THAT ARE GOING |
| TO ATTENDING THIS SCHOOL SEE THE 2017 FBC-B SECTION |
| 305.1 FOR AGE GROUP FOR AN EDUCATIONAL OCCUPANCY. |
| |
| 1C)UNDER THE HEADING OF APPLICABLE CODES LIST THE 2017 |
| EXISTING BUILDING CODE, LEVEL I ALTERATION. FOR A |
| CHANGE OF OCCUPANCY THE CODE REQUIRES US TO USE THE |
| 2017 EXISTING BUILDING CODE CHAPTER 10 FOR CHANGE OF |
| OCCUPANCY. SEE 2017 FBC-EXISTING BUILDING CODE SECTION |
| 1001.2.2.1 PARTIAL CHANGE OF OCCUPANCY. |
| WHERE THE OCCUPANCY CLASSIFICATION OR GROUP OF A |
| PORTION OF AN EXISTING BUILDING IS CHANGED, SECTION |
| 1012 SHALL APPLY. |
| |
| 1D) THE PLAN IS SILENT AS TO OCCUPANCY SEPARATION |
| REQUIREMENTS UNDER THE 2017 FBC-EXISTING BUILDING CODE |
| SECTIONS 1012.1.1 WITHOUT SEPARATION OR 1012.1.1.2 WITH |
| SEPARATION. |
| |
| 1E) 2017 EXISTING BUILDING CODE 1012.1.3 CHANGE OF |
| OCCUPANCY CLASSIFICATION BASED ON HAZARD CATEGORY. |
| |
| THE RELATIVE DEGREE OF HAZARD BETWEEN DIFFERENT |
| OCCUPANCY CLASSIFICATIONS SHALL BE DETERMINED IN |
| ACCORDANCE WITH THE CATEGORIES SPECIFIED IN TABLES |
| 1012.4, 1012.5 AND 1012.6. SUCH A DETERMINATION SHALL |
| BE THE BASIS FOR THE APPLICATION OF SECTIONS 1012.4 |
| THROUGH 1012.7. |
| PLEASE REVIEW IN THE 2017 EXISTING BUILDING CODE TABLE |
| 1012.4. YOU ARE GOING FROM A HIGHER HAZARD CATEGORY |
| FROM BUSINESS TO AN EDUCATIONAL OCCUPANCY. THE LOWER |
| THE NUMBER THE HIGHER THE HAZARD. BUSINESS BEING A 4 |
| TYPE HAZARD CATEGORY AND EDUCATIONAL BEING A 2 A HIGHER |
| HAZARD CATEGORY. |
| |
| 1F) 2017 EXISTING BUILDING CODE 1012.2.2 FIRE ALARM AND |
| DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY |
| CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF |
| OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES |
| A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED |
| ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS IN ACCORDANCE WITH SECTION 907 OF THE |
| FLORIDA BUILDING CODE, BUILDING AS REQUIRED FOR NEW |
| CONSTRUCTION. |
| |
| 1G) 2017 EXISTING BUILDING CODE 1012.1.4 ACCESSIBILITY. |
| ALL BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY |
| CLASSIFICATION SHALL COMPLY WITH SECTION 1012.8. |
| 2017 EXISTING BUILDING CODE 1012.8 ACCESSIBILITY. |
| EXISTING BUILDINGS THAT UNDERGO A CHANGE OF GROUP OR |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH THE |
| PROVISIONS OF THE FLORIDA BUILDING CODE, ACCESSIBILITY. |
| 2017 FBC-ACCESSIBILITY CODE 202.4.2 ACCESSIBLE FEATURES |
| IN THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF |
| ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE |
| ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO |
| THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL |
| SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE |
| MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE |
| COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE |
| ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE |
| ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| 1H) 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER |
| HAZARD CATEGORY. |
| |
| WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| 1012.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| EXCEPTIONS: |
| 1H)(1).STAIRWAYS SHALL BE ENCLOSED IN COMPLIANCE WITH |
| THE APPLICABLE PROVISIONS OF SECTION 903.1. |
| 2017 EXISTING BUILDING CODE SECTION 903.1 EXISTING |
| SHAFTS AND VERTICAL OPENINGS. EXISTING STAIRWAYS THAT |
| ARE PART OF THE MEANS OF EGRESS SHALL BE ENCLOSED IN |
| ACCORDANCE WITH SECTION 803.2.1 FROM THE HIGHEST WORK |
| AREA FLOOR TO, AND INCLUDING, THE LEVEL OF EXIT |
| DISCHARGE AND ALL FLOORS BELOW. |
| 1H)(2).EXISTING STAIRWAYS INCLUDING HANDRAILS AND |
| GUARDS COMPLYING WITH THE REQUIREMENTS OF CHAPTER 9 |
| SHALL BE PERMITTED FOR CONTINUED USE SUBJECT TO |
| APPROVAL OF THE CODE OFFICIAL. |
| 1H)(3).ANY STAIRWAY REPLACING AN EXISTING STAIRWAY |
| WITHIN A SPACE WHERE THE PITCH OR SLOPE CANNOT BE |
| REDUCED BECAUSE OF EXISTING CONSTRUCTION SHALL NOT BE |
| REQUIRED TO COMPLY WITH THE MAXIMUM RISER HEIGHT AND |
| MINIMUM TREAD DEPTH REQUIREMENTS. |
| 1H)(4).EXISTING CORRIDOR WALLS CONSTRUCTED ON BOTH |
| SIDES OF WOOD LATH AND PLASTER IN GOOD CONDITION OR |
| 1/2- INCH-THICK (12.7 MM) GYPSUM WALLBOARD SHALL BE |
| PERMITTED. SUCH WALLS SHALL EITHER TERMINATE AT THE |
| UNDERSIDE OF A CEILING OF EQUIVALENT CONSTRUCTION OR |
| EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF NEXT |
| ABOVE. |
| 1H)(5).EXISTING CORRIDOR DOORWAYS, TRANSOMS AND OTHER |
| CORRIDOR OPENINGS SHALL COMPLY WITH THE REQUIREMENTS IN |
| SECTIONS 805.5.1, 805.5.2 AND 805.5.3. |
| 1H)(6) .EXISTING DEAD-END CORRIDORS SHALL COMPLY WITH |
| THE REQUIREMENTS IN SECTION 805.6. |
| |
| 2) 2017 FBC-B SPECIAL DETAILED REQUIREMENTS BASED ON |
| USE AND OCCUPANCY. |
| 401.1 DETAILED USE AND OCCUPANCY REQUIREMENTS. IN |
| ADDITION TO THE OCCUPANCY AND CONSTRUCTION REQUIREMENTS |
| IN THIS CODE, THE PROVISIONS OF THIS CHAPTER APPLY TO |
| THE SPECIAL USES AND OCCUPANCIES DESCRIBED HEREIN. |
| 401.2 ADDITIONAL DESIGN CRITERIA./ 401.2.1 SCOPE. |
| 401.1 DETAILED USE AND OCCUPANCY REQUIREMENTS. IN |
| ADDITION TO THE PROVISIONS OF THIS CHAPTER, THE |
| FOLLOWING SPECIAL OCCUPANCIES, STANDARDS, REQUIREMENTS |
| AND CODES SHALL CONFORM TO THE FOLLOWING SECTIONS: |
| SECTION 468: SCHOOLS. |
| |
| 2A) 2017 FBC-B 468.3.2 GLARE FROM NATURAL LIGHT. |
| SOURCES OF NATURAL LIGHT IN INSTRUCTIONAL SPACES SHALL |
| BE GLAZED WITH GLARE REDUCING MATERIALS OR SHALL BE |
| SHIELDED TO PREVENT GLARE THAT CAN INTERFERE WITH |
| SEEING TASKS WITHIN THE INSTRUCTIONAL SPACE. |
| 468.3.7.5 GLARE ELIMINATION. ILLUMINATION OF |
| PERMANENTLY INSTALLED MARKERBOARDS, CHALKBOARDS, AND |
| OTHER INSTRUCTION AIDS SHALL BE DESIGNED TO ELIMINATE |
| GLARE AND SHADOWS. |
| |
| 2B) 468.3.5.5 WALLS. WALLS IN TOILET ROOMS SHALL BE |
| IMPERVIOUS TO A HEIGHT OF AT LEAST 4 FEET (1219 MM) |
| ABOVE THE FLOOR. |
| |
| 2C) 468.3.5.7.2 SOAP DISPENSERS FOR LIQUID, FOAM, OR |
| POWDERED SOAP SHALL BE PROVIDED AT ALL HANDWASHING |
| BASINS. |
| |
| 2D) 468.3.7.1 ILLUMINATION LEVEL IN |
| CLASSROOMS/INSTRUCTIONAL SPACES. ILLUMINATION AT THE |
| NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION |
| SPACE SHALL BE A MINIMUM OF 40 FOOTCANDLES (400 LUX). |
| |
| 2E) 468.3.7.2 ILLUMINATION UNIFORMITY IN CLASSROOMS/ |
| INSTRUCTION SPACES. LUMINARIES SHALL HAVE A CEILING |
| ARRANGEMENT OR BE POSITIONED AROUND THE WALLS SUCH THAT |
| A UNIFORMED ILLUMINATION LEVEL, WITHIN 10 FOOTCANDLES |
| (100 LUX), IS MAINTAINED AT THE STUDENTS REQUIRED |
| NORMAL TASK LEVEL FOR THE TYPE OF CLASSROOM/INSTRUCTION |
| SPACE. |
| |
| 2F) 468.3.7.3 BRIGHTNESS RATIO IN |
| CLASSROOMS/INSTRUCTIONAL SPACES. THE BRIGHTNESS RATIO |
| BETWEEN THE STUDENT TASK LEVEL AND THE INSTRUCTION AREA |
| OR AREAS OR VISUAL DISPLAY LOCATION SHALL BE ONE TO |
| FIVE OR LESS. |
| |
| 2G) 468.3.7.4 ILLUMINATION FAILURE OF GENERAL AND MEANS |
| OF EGRESS LUMINARIES. ILLUMINATION SYSTEMS SHALL BE |
| DESIGNED AND MAINTAINED SO THAT THE FAILURE OF ANY |
| SINGLE LIGHTING UNIT, SUCH AS AN ELECTRIC LUMINARY, |
| DOES NOT LEAVE ANY OCCUPIED SPACE OR MEANS OF EGRESS IN |
| THE DARK. (SEE SECTION 1008 FOR ADDITIONAL MEANS OF |
| EGRESS REQUIREMENTS.) |
| |
| 3) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| TFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |