2019-08-02 06:51:55 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. NO LOAD STUDY HAS BEEN PROVIDED PER NEC 220.87. |
| PROVIDE LOAD STUDY OF EXISTING SERVICE. |
| |
| 2. "LOAD CALCULATION" PROVIDED DOES NOT SHOW |
| CALCULATION FOR NEW LOAD ONLY SHOWS "250AMPS" ADDED. |
| PROVIDE LOAD CALCULATION SHOWING ADDITION OF NEW LOAD. |
| FBC 107.2.1 NEC 220. |
| |
| 3. SPECIFY LOCATION OF ELECTRICAL DATUM PLANE IN |
| RELATION TO HEIGHT OF DOCK/PIER FBC 107.2.1 |
| |
| 4 GROUND FAULT PROTECTION REQUIRED FOR NEW CIRCUIT |
| BREAKER FOR FEEDER THAT'S TO BE INSTALLED IN MSB. NEC |
| 555.3 |
| |
| 5 SPECIFY HEIGHT OF NEW JBOX TO BE INSTALLED. FBC |
| 107.2.1 NEC 555.9 |
| |
| 6 PROVIDE CUT SHEETS FOR PRODUCT APPROVAL OF PEDESTALS |
| AND PROPOSED PORTABLE POWER CABLES. FBC 107.2.1 NEC |
| 90.7, 110.2, 110.3B |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |
| FRANK GIAQUINTO III |
| ELECTRICAL INSPECTOR |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| [email protected] |
| CELL: 561-657-1653 |
| |
| |