Plan Review Notes For Permit 19071341 |
Permit Number |
19071341 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-01 09:09:41 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM | | (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) | | 805-6724 | | [email protected] | | | | 1ST REVIEW: FBC 2017 6TH EDITION | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED | | BELOW. | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | | 1. FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF | | PROTECTIVE DEVICES OR ASSEMBLIES: COLUMN HEADING | | ?ANCHOR SPACING?; VERIFY INFORMATION FROM PAGE 11; | | EXAMPLE ?? TAPCON, 40 (PSF), SPANS UP TO 9?-0?, C4 | | CONNECTION TYPE ANCHOR SPACING IS 9.4?. | | |
|