2019-07-29 06:54:35 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ELECTRICAL PERMIT REQUIRED. FBC 105.1 |
| |
| 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED BY THE |
| ELECTRICAL CONTRACTOR QUALIFIER. FS 471.003(2)(H); |
| 471.025; WPB FBC 107.2.1, 107.3.5 |
| |
| 3. PROVIDE ACCURATE LOAD CALCULATION INCLUDING ALL |
| LOADS (BOTH NEW AND EXISTING). NEC 220; FBC RE E3602.2 |
| |
| 4. SPECIFY WHAT SIZE TANKLESS WATER HEATER IS BEING |
| INSTALLED. SPEC SHEET PROVIDED SHOWS 3 DIFFERENT SIZES. |
| FBC 107.2.1 MORE INFORMATION REQUIRED. |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |