Plan Review Notes
Plan Review Notes For Permit 19071302
Permit Number 19071302
Review Stop P
Sequence Number 1
Notes
Date Text
2019-08-01 14:46:0808/01/2019 1ST PLUMBING REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. A GENERAL CONTRACTOR CAN NOT DO PLUMBING WORK PER
 SEC 489.105 OF THE FLORIDA STATUES. PLEASE PROVIDE A
 SEPARATE PERMIT WITH THIS APPLICATION FOR ALL PLUMBING
 WORK FROM A LICENSE PLUMBING CONTRACTOR IN ACCORDANCE
 WITH 489.105 AND 489.113
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  