2019-08-12 07:09:54 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19071222 |
| ADD: 3800 WASHINGTON RD. SUITE: 1003 |
| CONT: NARUS MODERN CONCEPTS LLC |
| TEL: 561-360-6589 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: MONDAY/ AUGUST 12/2019 |
| ACTION: DENIED |
| |
| 1) PLEASE NOTE SHEET A-001 IN THE TITLEBLOCK THE PLAN |
| STATES THE PLANS WERE CREATED UNDER THE OFFICE OF |
| LABERGE & MENARD INC. AN ARCHITECTURAL C OA |
| (AA26003344) BUT NO SIGNATURE AN SEAL. |
| |
| 61G1-16.004 TITLE BLOCK. ARCHITECT. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED |
| AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN |
| THE FOLLOWING INFORMATION: |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION |
| NUMBER OF THE PERSON SEALING THE DOCUMENT. |
| |
| 2) THE SUITE NUMBER IS 1003, IT IS NOT CLEAR IF THIS |
| UNIT IS ON THE 1ST FLOOR OR THE 10TH FLOOR. FOR THIS |
| REVIEW IT IS ASSUMED THE 10TH FLOOR. |
| |
| 2) SHEET A-001 IT WOULD APPEAR THAT SOMEONE HAS HAND |
| DRAWN ELECTRICAL SYSTEMS ON WHAT APPEARS TO BE AN |
| ARCHITECTS PLAN SINCE THERE IS AN ARCHITECTURAL FIRMS |
| NAME IN THE TITLE BLOCK BUT NOT SIGNED AND SEALED. WITH |
| THE ARCHITECTS FIRM NAME AND LICENSE NUMBER IT IS |
| ASSUMED THIS PLAN WAS A DESIGN OF THE ARCHITECTURAL |
| FIRM AND CANNOT BE WRITTEN OR DRAWN ON WITH THE |
| EXCEPTION OF THE ARCHITECT OF RECORD. |
| |
| FL ADMIN CODE 61G16.003(1) ARCHITECTS. PLANS, |
| SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY |
| THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC |
| RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN |
| PROFESSIONAL AFFIXED TO THE DOCUMENT. |
| PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE |
| ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST |
| AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC |
| 61G1-16.003. |
| |
| 3) PLEASE NOTE THAT QEP 72000Q/ 72003Q & 72008Q DO HAVE |
| PRODUCT TESTING REPORTS ON FILE WITH THE CITY OF WEST |
| PALM BEACH BUILDING DIVISION FOR TILE ON 6 INCH |
| CONCRETE SLAB, NONE HAVE EVER BEEN SUBMITTED FOR WOOD |
| FLOORING. ACOUSTICORK A DIVISION OF AMORIM CORK |
| COMPOSITES WHO ALSO OWNS QEP UNDERLAYMENT?S DOES SHOW |
| ONLINE A TEST NUMBER NGC 7008139/40- NGC 5008072 FOR |
| GLUED WOOD SYSTEM ON A 6 INCH CONCRETE FLOOR SYSTEM, |
| BUT NONE HAS EVER BEEN SUBMITTED. WE HAVEN?T SEEN A |
| FLAME TEST WITH WOOD PRODUCTS AND THE UNDERLAYMENT |
| EITHER PLEASE PROVIDE TEST RESULTS FOR THE FOLLOWING: |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) |
| FOR WOOD AND WOOD LAMINATE FLOORING ALL NEED TO HAVE |
| HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO |
| THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH |
| CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS, |
| PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR |
| AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 90. |
| |
| 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |