Plan Review Notes
Plan Review Notes For Permit 19071222
Permit Number 19071222
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-12 07:09:542017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071222
 ADD: 3800 WASHINGTON RD. SUITE: 1003
 CONT: NARUS MODERN CONCEPTS LLC
 TEL: 561-360-6589
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY/ AUGUST 12/2019
 ACTION: DENIED
  
 1) PLEASE NOTE SHEET A-001 IN THE TITLEBLOCK THE PLAN
 STATES THE PLANS WERE CREATED UNDER THE OFFICE OF
 LABERGE & MENARD INC. AN ARCHITECTURAL C OA
 (AA26003344) BUT NO SIGNATURE AN SEAL.
  
 61G1-16.004 TITLE BLOCK. ARCHITECT.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS THAT ARE REQUIRED TO BE SIGNED
 AND SEALED. THE TITLE BLOCK MUST, AT A MINIMUM, CONTAIN
 THE FOLLOWING INFORMATION:
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) THE PRINTED NAME AND THE LICENSE/REGISTRATION
 NUMBER OF THE PERSON SEALING THE DOCUMENT.
  
 2) THE SUITE NUMBER IS 1003, IT IS NOT CLEAR IF THIS
 UNIT IS ON THE 1ST FLOOR OR THE 10TH FLOOR. FOR THIS
 REVIEW IT IS ASSUMED THE 10TH FLOOR.
  
 2) SHEET A-001 IT WOULD APPEAR THAT SOMEONE HAS HAND
 DRAWN ELECTRICAL SYSTEMS ON WHAT APPEARS TO BE AN
 ARCHITECTS PLAN SINCE THERE IS AN ARCHITECTURAL FIRMS
 NAME IN THE TITLE BLOCK BUT NOT SIGNED AND SEALED. WITH
 THE ARCHITECTS FIRM NAME AND LICENSE NUMBER IT IS
 ASSUMED THIS PLAN WAS A DESIGN OF THE ARCHITECTURAL
 FIRM AND CANNOT BE WRITTEN OR DRAWN ON WITH THE
 EXCEPTION OF THE ARCHITECT OF RECORD.
  
 FL ADMIN CODE 61G16.003(1) ARCHITECTS. PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS PREPARED BY
 THE DESIGN PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE DESIGN
 PROFESSIONAL AFFIXED TO THE DOCUMENT.
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003.
  
 3) PLEASE NOTE THAT QEP 72000Q/ 72003Q & 72008Q DO HAVE
 PRODUCT TESTING REPORTS ON FILE WITH THE CITY OF WEST
 PALM BEACH BUILDING DIVISION FOR TILE ON 6 INCH
 CONCRETE SLAB, NONE HAVE EVER BEEN SUBMITTED FOR WOOD
 FLOORING. ACOUSTICORK A DIVISION OF AMORIM CORK
 COMPOSITES WHO ALSO OWNS QEP UNDERLAYMENT?S DOES SHOW
 ONLINE A TEST NUMBER NGC 7008139/40- NGC 5008072 FOR
 GLUED WOOD SYSTEM ON A 6 INCH CONCRETE FLOOR SYSTEM,
 BUT NONE HAS EVER BEEN SUBMITTED. WE HAVEN?T SEEN A
 FLAME TEST WITH WOOD PRODUCTS AND THE UNDERLAYMENT
 EITHER PLEASE PROVIDE TEST RESULTS FOR THE FOLLOWING:
  
 BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B
 2017)
 FOR WOOD AND WOOD LAMINATE FLOORING ALL NEED TO HAVE
 HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO
 THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS
 LISTED UNDER EACH OF THE STANDARDS FOR A 6 INCH
 CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING:
 PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH:
  
 3A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 3B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 3C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2.
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER