Plan Review Notes
Plan Review Notes For Permit 19071157
Permit Number 19071157
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-24 14:06:45RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- FLAT ROOF NOA 17-0824.11 SUBMITTED: SELECTED
 ASSEMBLY ON PAGE 27 OF 32 DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED
 RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER
 AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7
 ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE
 DESIGN PRESSURES REQUIRED BY SEC. R301.2.1
 FBC-RESIDENTIAL.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,