2019-07-24 14:06:45 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- FLAT ROOF NOA 17-0824.11 SUBMITTED: SELECTED |
| ASSEMBLY ON PAGE 27 OF 32 DOESN'T MEET THE DESIGN |
| PRESSURES FOR ALL ROOF ZONES. PROVIDE SIGNED AND SEALED |
| RAS 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER |
| AND CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7 |
| ON LAST PAGE OF NOA. NEED THE CALCULATIONS TO MEET THE |
| DESIGN PRESSURES REQUIRED BY SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |