Plan Review Notes For Permit 19071126 |
Permit Number |
19071126 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-01 07:08:09 | 08/01/2019 1ST PLUMBING/POOL REVIEW**DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THIS POOL DOES NOT HAVE A HEATER AND IN THE DYNAMIC | | CALCULATIONS YOU HAVE A HEATER IN THE SUMS, PLEASE TAKE | | OUT THE HEATER AND REFER OR ADJUST PUMP SIZE SHOWING | | YOUR WORK ON CURVE AND CALCULATIONS, WPB AMENDMENTS TO | | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|