Plan Review Notes For Permit 19071115 |
Permit Number |
19071115 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-01-23 14:49:25 | PLUMBING COMMENTS: APPROVED W/PROVISO | | 1. HAVING NOTED THE EXISTING VTR ON THE REVISED | | PLUMBING RISER, IT IS DETERMINED THAT AT THE PLUMBING | | INSPECTOR?S DISCRETION, ANY EXISTING PLUMBING | | INFRASTRUCTURE SHALL BE SUBJECT TO INSPECTION FOR CODE | | COMPLIANCE. THIS MAY REQUIRE PROVIDING DOCUMENTATION | | OF, OPENING OF WALLS AND/OR FLOORS, PRESSURE TESTS, | | VIDEO CAM OF UNDERGROUND SANITARY, ETC., AS DETERMINED | | BY THE PLUMBING INSPECTOR. PLEASE CALL TIM LARGE AT | | 561-805-6692 FOR ADDITIONAL INFORMATION AND/OR | | CLARIFICATION. | | 2. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD | | INSPECTOR'S APPROVAL | | 3. SHOWER COMPARTMENT SHALL COMPLY WITH THE | | REQUIREMENTS OF FBC RES P2709 | | 4. PLEASE NOTE THAT A GAS TANKLESS WATER HEATER HAS | | BEEN ADDED TO THE PLAN. AS A RESULT, A GAS PLAN SHALL | | BE SUBMITTED SHOWING ALL INFORMATION REQUIRED BY WPB | | FBC 107.3.5.3 (13) AND A SEPARATE GAS PERMIT APPLIED | | FOR. | | 5. PLEASE NOTE THAT THE SUBMITTED RINNAI RU199IN GAS | | TANKLESS WATER HEATER IS DESIGNED FOR INDOOR USE AND | | NOT OUTDOORS AND THE DOCUMENT PROVIDED IS FOR | | MARKETING, NOT THE MANUFACTURER?S SPECIFICATION/DATA. | | WHEN APPLYING FOR GAS PERMIT PROVIDE MANUFACTURER?S | | SPECIFICATION/DATA SHEETS FOR THE APPROPRIATE OUTDOOR | | UNIT. | | |
|