2019-07-24 13:52:49THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE NATURE OF THE WORK MAY REQUIRE THE FIRE
 SPRINKLERS ORIENTATION BE MODIFIED FROM PENDENT TO
 UPRIGHT.
  
 PER NFPA 13
 8.5 POSITION, LOCATION, SPACING, AND USE OF SPRINKLERS.
 8.5.1 GENERAL.
 8.5.1.1 SPRINKLERS SHALL BE LOCATED, SPACED, AND
 POSITIONED IN
 ACCORDANCE WITH THE REQUIREMENTS OF SECTION 8.5.
 8.5.1.2 SPRINKLERS SHALL BE POSITIONED TO PROVIDE
 PROTECTION
 OF THE AREA CONSISTENT WITH THE OVERALL OBJECTIVES OF
 THIS STANDARD
 BY CONTROLLING THE POSITIONING AND ALLOWABLE AREA OF
 COVERAGE
 FOR EACH SPRINKLER.
  
 CONSULTATION WITH A FIRE SPRINKLER CONTRACTOR IS
 RECOMMENDED TO ENSURE COMPLIANCE.
  
 PLEASE ENSURE PROPER FIRE SPRINKLER HEAD ORIENATION.
  
  
  
 2) ANY WORK ON THE FIRE SPRINKLER SYSTEM SHALL BE DONE
 UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 PLEASE PROVIDE A NOTE OF COMPLAINCE.
  
  
  
 3) THERE IS AN INDCATION OF FIRE ALARM EQUIPMENT.
  
 ALL WORK OR RELOCATION ON HE FIRE ALARM SYSTEM SHALL BE
 DONE UNDER SEPARATE PERMIT AND SHOP DRAWINGS.
  
 THE FIRE ALARM SYSTEM SHALL BE MAINTAINED HROUGHOUT
 DEOM AND RECONSTRUCTION.
  
 PLEASE PROVIDE A NOTE OF COMPLAINCE.
  
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL