2019-09-24 12:29:401ST REVIEW: 19071062
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. D-1 SANITARY ISOMETRIC SHOW THE CONNECTION
 POINT OF THE 2ND FLOOR SANITARY PIPING TO THE BUILDING
 DRAIN OR SEWER. PER WPB AMEND TO FBC 107.3.5.1.3(13),
 107.2.1
  
 2. PLEASE PROVIDE A WATER ISOMETRIC SHOWING REQUIRED
 AIR HAMMER ARRESTORS AND ALL SHUT OFF VALVES AND WATER
 HEATERS.PER WPB AMEND TO FBC 107.3.5.1.3(13), 107.2.1
  
 3. SHOW LOCATION OF THE WATER HEATERS ON THE FLOOR
 PLAN.PER WPB AMEND TO FBC 107.2.1
  
 4. PLEASE PLACE NOTE ON THE PLAN SHUT OF VALVES FOR THE
 WASHING MACHINE SHALL BE ACCESSIBLE WITHOUT MOVING
 APPLIANCE. PER FBC PL 606.3
  
 5. EACH UNIT SHALL HAVE A SEPARATE SHUT OFF VALVE SHOWN
 ON THE FLOOR PLAN AND ISOMETRIC DRAWING.PER FBC PL
 606.1(6)
  
 6. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED WHERE
 QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTRUCTIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010. PER FBC PL 604.9
  
 7. PROVIDE MANUFACTURE SIZING TABLES OR CALCULATIONS,
 SPECIFICATION AND INSTILLATION GUIDE FOR THE TANKLESS
 WATER HEATERS. PER WPB AMEND TO FBC 107.2.1
  
 8. PLEASE PLACE NOTE ON PLAN ALL PLUMBING FIXTURES
 SHALL COMPLY WITH FBC PL 405.3.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  