2019-09-24 08:45:172017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071062 / HISTORIC BUILDING
 ADD: 809 6TH ST.
 CONT: SOUTH FLORIDA?S BEST CONSTRUCTION
 TEL: 561-294-8300
 E-MAIL: SF/[email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. SEPT. 24/ 2019
 ACTION: DENIED
  
 1) PLEASE NOTE THE COVERSHEET A-1 INDICATES THIS IS A
 LEVEL III ALTERATION. THE LAST KNOWN USE (OCCUPANCY
 R-3) FOR THIS BUILDING WAS A PERMIT 9700268
 MISCELLANEOUS FLOOR REPAIRS AN OWNER/ BUILDER PERMIT.
 THIS MADE THE OCCUPANCY TYPE A R3 SINGLE FAMILY
 RESIDENCE. THE OWNER BROUGHT IN THEIR HOMESTEAD TAX
 EXEMPTION AS PART OF THEIR PROOF OF OWNERSHIP. IN 2014
 ANOTHER PERMIT WAS APPLIED FOR 14120093 TO CHANGE THE
 OCCUPANCY CLASSIFICATION FROM A R3 SINGLE FAMILY
 DWELLING TO AN R2 A 4 UNIT APARTMENT BUILDING. THIS
 PERMIT HAS NEVER BEEN ISSUED AND WAS REVOKED. 4/21/2017
 THE OWNER AND CONTRACTOR WERE ADVISED TO RE-APPLY FOR
 THE PERMIT THAT HAD NEVER BEEN ISSUED. REVOKED
 9/15/2017.
  
 THIS IS A CHANGE OF USE PERMIT UNDER THE 2018
 FBC-EXISTING BUILDING CODE. 1001.2.1 CHANGE OF USE. ANY
 WORK UNDERTAKEN IN CONNECTION WITH A CHANGE IN USE THAT
 DOES NOT INVOLVE A CHANGE OF OCCUPANCY CLASSIFICATION
 OR A CHANGE TO ANOTHER GROUP WITHIN AN OCCUPANCY
 CLASSIFICATION SHALL CONFORM TO THE APPLICABLE
 REQUIREMENTS FOR THE WORK AS CLASSIFIED IN CHAPTER 5
 AND TO THE REQUIREMENTS OF SECTIONS 1002 THROUGH 1011.
 EXCEPTION: AS MODIFIED IN SECTION 1205 FOR HISTORIC
 BUILDINGS.
  
 2) PLEASE REVIEW SECTION 1003.1 OF THE 2017 EXIST.
 BUILDING CODE. BUILDING ELEMENTS AND MATERIALS IN
 PORTIONS OF BUILDINGS UNDERGOING A CHANGE OF OCCUPANCY
 CLASSIFICATION SHALL COMPLY WITH SECTION 1012.
  
 EXISTING BUILDING CODE1012.2 FIRE PROTECTION SYSTEMS.
 FIRE PROTECTION SYSTEMS SHALL BE PROVIDED IN ACCORDANCE
 WITH SECTIONS 1012.2.1 AND 1012.2.2.
  
 2A) 2017 EXISTING BUILDING CODE. 1012.2.1 FIRE
 SPRINKLER SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF
 OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT
 FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER
 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES
 AN AUTOMATIC FIRE SPRINKLER SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
  
 2017 FBC-B [F]903.2.8 GROUP R. AN AUTOMATIC SPRINKLER
 SYSTEM INSTALLED IN ACCORDANCE WITH SECTION 903.3 SHALL
 BE PROVIDED THROUGHOUT ALL BUILDINGS WITH A GROUP R
 FIRE AREA. F]903.3 INSTALLATION REQUIREMENTS. AUTOMATIC
 SPRINKLER SYSTEMS SHALL BE DESIGNED AND INSTALLED IN
 ACCORDANCE WITH SECTIONS 903.3.1 THROUGH 903.3.8.
  
 2017 FBC-B F]903.3.1.2 NFPA 13R SPRINKLER SYSTEMS.
 AUTOMATIC SPRINKLER SYSTEMS IN GROUP R OCCUPANCIES UP
 TO AND INCLUDING FOUR STORIES IN HEIGHT IN BUILDINGS
 NOT EXCEEDING 60 FEET (18 288 MM) IN HEIGHT ABOVE GRADE
 PLANE SHALL BE PERMITTED TO BE INSTALLED THROUGHOUT IN
 ACCORDANCE WITH NFPA 13R.
  
 2B) 2017 EXISTING BUILDING CODE SECTION 1012.2.2 FIRE
 ALARM AND DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF
 OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT
 FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER
 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES
 A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS.
 907.2.9 GROUP R-2. FIRE ALARM SYSTEMS AND SMOKE ALARMS
 SHALL BE INSTALLED IN GROUP R-2 OCCUPANCIES AS REQUIRED
 IN SECTIONS 907.2.9.1 THROUGH 907.2.9.3.
 [F]907.2.9.1 MANUAL FIRE ALARM SYSTEM. A MANUAL FIRE
 ALARM SYSTEM THAT ACTIVATES THE OCCUPANT NOTIFICATION
 SYSTEM IN ACCORDANCE WITH SECTION 907.5 SHALL BE
 INSTALLED IN GROUP R-2 OCCUPANCIES WHERE ANY OF THE
 FOLLOWING CONDITIONS APPLY:
 ANY DWELLING UNIT OR SLEEPING UNIT IS LOCATED MORE THAN
 ONE STORY BELOW THE HIGHEST LEVEL OF EXIT DISCHARGE OF
 EXITS SERVING THE DWELLING UNIT OR SLEEPING UNIT.
  
 3) THE SHEET A1 WILL NEED TO PROVIDE IF TRANSIENT OR
 NON-TRANSIENT, THIS WILL AFFECT IF ACCESSIBILITY
 BECOMES AN ISSUE, TRANSIENT MAY ALSO BECOME A R-1
 OCCUPANCY CLASSIFICATION. 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION, 107. 3.5.1.2 MINIMUM PLAN REVIEW
 CRITERIA COMMERCIAL BUILDING. 2017 FBC-B 310.1.
  
 4) THE SHEET - A1 UNDER THE HEADING SCOPE OF WORK NOTES
 1,2 & 9 INDICATE THERE WERE TO BE NOA?S SUBMITTED UNDER
 THIS REVIEW. THESE PRODUCT APPROVALS WERE TO BE FOR
 IMPACT WINDOWS, SOLID EXTERIOR DOORS AND TILE ROOF
 SYSTEM. NO PRODUCT WERE SUBMITTED. COMPLY WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS
 (B) WINDOWS & MULLIONS
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 5) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2014 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURERS INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 6A) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 6B) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 7) THE SHEET - A1 UNDER THE HEADING SCOPE OF WORK NOTES
 6 & 8 BOTH REFER TO SHEET S-1. THIS SHEET IS NOT
 INCLUDED IN THE SET OF PLANS NOR IN THE PLAN LEGEND.
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. NOTE 6
 INDICATES ON SHEET S-1 THERE ARE TENANT SEPARATION WALL
 AND CEILING DETAILS (HORIZONTAL SEPARATION OF FIRE
 AREAS).
  
 7A) SEMI-COMPLIED. THE SHEET - A1 WILL NEED TO SHOW ONE
 HOUR FIRE RATED WALL ON BOTH SIDES OF THE STAIR
 (INTERIOR WALLS) ON SHEET A1 AND ON SHEET A2 ( WALL
 LEGEND SHOWS 1 HOUR RATED), BUT IT REFERS TO SHEET D-1
 FOR DETAIL. THE WALL DETAIL IS FOR TENANT SEPARATION
 WALLS WITH ? DRYWALL. THE PLANS ARE SILENT ON SHEET A1
 THE FIRE RATING ON THE CEILING JUST BENEATH THE STAIR
 STRINGER. PLEASE REVIEW SECTION:
 2017 FBC-B 1011.7.3 ENCLOSURES UNDER INTERIOR
 STAIRWAYS. THE WALLS AND SOFFITS WITHIN ENCLOSED USABLE
 SPACES UNDER ENCLOSED AND UNENCLOSED STAIRWAYS SHALL BE
 PROTECTED BY 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION
 OR THE FIRE-RESISTANCE RATING OF THE STAIRWAY
 ENCLOSURE, WHICHEVER IS GREATER. ACCESS TO THE ENCLOSED
 SPACE SHALL NOT BE DIRECTLY FROM WITHIN THE STAIRWAY
 ENCLOSURE. EXCEPTION: SPACES UNDER STAIRWAYS SERVING
 AND CONTAINED WITHIN A SINGLE RESIDENTIAL DWELLING UNIT
 IN GROUP R-2 OR R-3 SHALL BE PERMITTED TO BE PROTECTED
 ON THE ENCLOSED SIDE WITH 1/2-INCH GYPSUM BOARD IN
 BUILDINGS EQUIPPED THROUGHOUT WITH AN AUTOMATIC
 SPRINKLER SYSTEM IN ACCORDANCE WITH 903.3.1.1. NOT A
 D-13 OR R-13 SYSTEM.
  
 7B) SHEET D-1 TENANT SEPARATION WALLS WILL NEED TO SHOW
 COMPLIANCE WITH SECTION 708.3 OF THE 2017 FBC-B. &08.3
 FIRE RESISTANCE RATING BETWEEN DWELLING UNITS NOT LESS
 THAN 1 HOUR. AGAIN THE EXCEPTION IS WHEN FULLY
 SPRINKLERED WITH A SPRINKLER SYSTEM THAT CONFORMS TO
 903.3.1.1. THEN A ? HOUR FIRE RATING BETWEEN UNITS IS
 ACCEPTABLE IN TYPE V-B CONSTRUCTION.
  
 7C) SHEET A1 & A2 BOTH INDICATE THE USE OF A 25 SINGLE
 HUNG WINDOW. PLEASE PROVIDE FROM THE MANUFACTURER THE
 SIZE OF WINDOW THIS REPRESENTS. THIS SHOULD ALSO MATCH
 UP WITH THE SIZING CHARTS ON THE PRODUCT APPROVALS
 SUBMITTED FOR WINDOWS. THEY MUST COMPLY WITH THE
 REQUIREMENTS FOR EMERGENCY ESCAPE OPENINGS FOR SLEEPING
 ROOMS. 2017 FBC-B 1030.2.(1-4).
  
 8) THE PLANS DO NOT INDICATE ON THE 2ND FLOOR WHAT TYPE
 OF NEW FLOOR COVERING ARE TO BE INSTALLED. PLEASE
 PROVIDE CODE COMPLIANCE FOR TILE, STONE, MARBLE, VINYL
 AND WOOD FLOORING ALL NEED TO HAVE HAD THE SOUND
 UNDERLAYMENT TESTED FLOOR ASSEMBLIES TO THE FOLLOWING
 STANDARDS AND MEET THE QUALIFICATIONS LISTED UNDER EACH
 OF THE STANDARDS FOR A 6 INCH CONCRETE FLOOR ASSEMBLY/
 NO DROPPED CEILING. PLEASE PROVIDE TEST REPORTS NOT
 JUST PLACE THE CODE SECTION ON THE PLANS, SHOW
 COMPLIANCE WITH:
  
 8A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
  
 8B) FBC-B 2017 1207.2 AIR-BORNE SOUND. WALLS,
 PARTITIONS AND FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR
 AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E
 90.
  
 8C) TYPE III-TYPE V CONSTRUCTION: FBC-B-2017 720.2
 CONCEALED INSTALLATION. INSULATING MATERIALS, WHERE
 CONCEALED AS INSTALLED IN BUILDINGS OF ANY TYPE OF
 CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT
 MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE
 THAN 450.
  
 FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS
 A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL
 MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A
 MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723.
  
 9) SHEET A-3 PROVIDES THE WIND DESIGN DATA AND WORST
 CASE PRESSURES (10 SQ. FT.) FOR WALL ZONES 4 & 5 BUT
 THERE ARE NO PRESSURES PROVIDED FOR THE ROOF ZONES 1, 2
 & 3 FOR PITCHED ROOFS FROM 7 TO 27 DEGREES.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.(5) 5. DESIGN WIND
 PRESSURES TO BE USED FOR EXTERIOR COMPONENTS AND
 CLADDING MATERIALS (ROOFING).
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. ONE SET OF
 PLANS WILL HAVE TO BE TAKEN (BY THE CONTRACTOR OR
 REPRESENTATIVE) TO THE PALM BEACH COUNTY IMPACT FEE
 OFFICE LOCATED AT 2300 N. JOG RD. ROOMS 2W01-2W14 WEST
 PALM BEACH, FL. THE ACTUAL PERMIT SET OF PLANS MUST BE
 STAMPED BY THAT OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION. PLEASE CALL
 (561)233-5025 FOR MORE INFORMATION.
  
 11) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER