Plan Review Notes
Plan Review Notes For Permit 19071033
Permit Number 19071033
Review Stop B
Sequence Number 2
Notes
Date Text
2019-09-16 10:30:24RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
  
 ARCHITECTS-ENGINEERS
 FLORIDA STATUTE 553.80(2)(B):
 WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS
 DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN
 ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING
 CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS
 REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO
 CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY
 NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO,
 EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY,
 ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL,
 MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER
 REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING
 COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL
 GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH
 REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION,
 A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE
 PERMIT FEE ATTRIBUTED TO PLANS REVIEW
  
  
 ORIGINAL COMMENT:
 1- STRUCTURAL PLANS SUBMITTED ARE FOR THE INSTALLATION
 OF SOLAR PV SYSTEMS ON ROOFS WITH ROOF TILES. THIS IS A
 HOUSE WITH ROOF SHINGLES. THE PROPOSED INSTALLATION
 DOESN'T MATCH ACTUAL CONDITIONS. REVISE AS REQUIRED.
 SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1
 FBC-RESIDENTIAL.
  
 RESPONSE:
 PLANS SUBMITTED ARE THE SAME. NO CHANGES WERE DONE.
 PLANS DON'T APPLY TO THE PROPOSED SITE SPECIFIC
 INSTALLATION. PROVIDE COMPLETE DRAWINGS FOR SITE
 SPECIFIC INSTALLATION.
 NOTE: CONTRACTOR STATED ON THE RE-SUBMITTAL FORM THAT
 SOLAR PANELS ARE GOING TO BE INSTALLED ON THE FLAT ROOF
 OF THE HOUSE. PLANS AND DESIGN CRITERIA NEED TO MATCH
 THIS PROPOSED INSTALLATION. REVISE PLANS AS REQUIRED TO
 MATCH PROPOSED INSTALLATION.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
  
 ORIGINAL COMMENT:
 2- STRUCTURAL ATTACHMENT TO THE ROOF OF THE HOUSE IS
 NOT CLEAR. FLORIDA PRODUCT APPROVAL FL21074.R4
 REFERENCED ON DRAWING S-03 IS ONLY FOR THE "ROOF SOLAR
 PEDESTAL". THIS PRODUCT APPROVAL ONLY EVALUATES THE
 SOLAR PEDESTAL ADHERED TO TOP OF FOAM ADHESIVE. ALSO,
 THE DESIGN OF THE ROOF ADHESIVE TO THE BUILDING
 STRUCTURE IS OUTSIDE THE SCOPE OF THIS PRODUCT
 APPROVAL. SEE ITEMS # 12.1 AND 12.2 OF THE LIMITATIONS
 AND CONDITIONS OF USE ON PAGE 3 OF 7 OF THIS PRODUCT
 APPROVAL. ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE
 DESIGN ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE
 DESIGN ATTACHMENT OF THE FOAM ADHESIVE TO THE BUILDING
 STRUCTURE. NEED TO SHOW HOW THE SURFACE RECEIVING THE
 FOAM ADHESIVE WILL TRANSFER THE LOADS. SEC. 107.2.1.2
 CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: KEEP IN CONSIDERATION THAT THIS HOUSE HAS ROOF
 SHINGLES. ALSO, NEED PRODUCT APPROVAL FOR FOAM ADHESIVE
 LISTING THE SURFACE WHERE THE FOAM IS GOING TO BE
 ADHERED TO.
  
 RESPONSE:
 ENGINEER DIDN'T PROVIDE A COMPLETE SITE SPECIFIC DESIGN
 ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE LOAD
 PATH FROM THE ADHESIVE TO THE EXISTING ROOF STRUCTURE.
 ENGINEER TO COORDINATE COMPLETE ANALYSIS AND
 DETAILS/SPECIFICATIONS WITH THE PROPOSED INSTALLATION
 ON THE EXISTING FLAT ROOF AS SPECIFIED BY THE
 CONTRACTOR SUBMITTING THE PERMIT APPLICATION.
 NOTE: EXISTING ROOF WAS REPLACED IN 2003. UPLIFT TEST
 MAY BE REQUIRED TO DEMONSTRATE THAT EXISTING ROOF
 MEMBRANE WILL RESISTS THE ADDITIONAL WIND LOADS.
  
  
 ORIGINAL COMMENT:
 3- ENGINEER OF RECORD NEEDS TO PROVIDE ALL HIS
 INFORMATION ON THE TITLE BLOCK OF ALL DRAWINGS AS
 REQUIRED BY SEC. 61G15-23.001(4) F.A.C.
  
 RESPONSE:
 ENGINEER'S INFORMATION IS NOT PROVIDED ON THE TILE
 BLOCK OF DRAWINGS SUBMITTED.
  
  
 ORIGINAL COMMENT:
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 SEC. 61G20-3.001 F.A.C. FOR:
 A) ROOF SOLAR PEDESTAL SPECIFIED ON PLANS.
  
 RESPONSE:
 ONE ONE COPY SUBMITTED. NEED TWO COPIES.
  
 ORIGINAL COMMENT:
 B) FOAM ADHESIVE SPECIFIED ON PLANS. NEED PRODUCT
 APPROVAL FOR FOAM ADHESIVE LISTING THE SURFACE WHERE
 THE FOAM IS GOING TO BE ADHERED TO.
  
 RESPONSE:
 NEED PRODUCT APPROVAL LISTING THE SURFACE WHERE THE
 FOAM IS GOING TO BE ADHERED TO. PRODUCT APPROVAL
 SUBMITTED IS FOR INSTALLATION ON ROOF TILE UNDERLAYMENT
 ONLY.
  
  
 PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND
 REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE
 DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD
 DRAWINGS/DOCUMENTS FOR REFERENCE.
  
 IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE
 TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE
 COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  