2019-09-16 10:30:24 | RESIDENTIAL (R3) SECOND BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| |
| ARCHITECTS-ENGINEERS |
| FLORIDA STATUTE 553.80(2)(B): |
| WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS |
| DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| PERMIT FEE ATTRIBUTED TO PLANS REVIEW |
| |
| |
| ORIGINAL COMMENT: |
| 1- STRUCTURAL PLANS SUBMITTED ARE FOR THE INSTALLATION |
| OF SOLAR PV SYSTEMS ON ROOFS WITH ROOF TILES. THIS IS A |
| HOUSE WITH ROOF SHINGLES. THE PROPOSED INSTALLATION |
| DOESN'T MATCH ACTUAL CONDITIONS. REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. SEC. R301.2.1 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| PLANS SUBMITTED ARE THE SAME. NO CHANGES WERE DONE. |
| PLANS DON'T APPLY TO THE PROPOSED SITE SPECIFIC |
| INSTALLATION. PROVIDE COMPLETE DRAWINGS FOR SITE |
| SPECIFIC INSTALLATION. |
| NOTE: CONTRACTOR STATED ON THE RE-SUBMITTAL FORM THAT |
| SOLAR PANELS ARE GOING TO BE INSTALLED ON THE FLAT ROOF |
| OF THE HOUSE. PLANS AND DESIGN CRITERIA NEED TO MATCH |
| THIS PROPOSED INSTALLATION. REVISE PLANS AS REQUIRED TO |
| MATCH PROPOSED INSTALLATION. |
| SEC. R301.2.1 FBC-RESIDENTIAL. |
| |
| |
| ORIGINAL COMMENT: |
| 2- STRUCTURAL ATTACHMENT TO THE ROOF OF THE HOUSE IS |
| NOT CLEAR. FLORIDA PRODUCT APPROVAL FL21074.R4 |
| REFERENCED ON DRAWING S-03 IS ONLY FOR THE "ROOF SOLAR |
| PEDESTAL". THIS PRODUCT APPROVAL ONLY EVALUATES THE |
| SOLAR PEDESTAL ADHERED TO TOP OF FOAM ADHESIVE. ALSO, |
| THE DESIGN OF THE ROOF ADHESIVE TO THE BUILDING |
| STRUCTURE IS OUTSIDE THE SCOPE OF THIS PRODUCT |
| APPROVAL. SEE ITEMS # 12.1 AND 12.2 OF THE LIMITATIONS |
| AND CONDITIONS OF USE ON PAGE 3 OF 7 OF THIS PRODUCT |
| APPROVAL. ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE |
| DESIGN ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE |
| DESIGN ATTACHMENT OF THE FOAM ADHESIVE TO THE BUILDING |
| STRUCTURE. NEED TO SHOW HOW THE SURFACE RECEIVING THE |
| FOAM ADHESIVE WILL TRANSFER THE LOADS. SEC. 107.2.1.2 |
| CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: KEEP IN CONSIDERATION THAT THIS HOUSE HAS ROOF |
| SHINGLES. ALSO, NEED PRODUCT APPROVAL FOR FOAM ADHESIVE |
| LISTING THE SURFACE WHERE THE FOAM IS GOING TO BE |
| ADHERED TO. |
| |
| RESPONSE: |
| ENGINEER DIDN'T PROVIDE A COMPLETE SITE SPECIFIC DESIGN |
| ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE LOAD |
| PATH FROM THE ADHESIVE TO THE EXISTING ROOF STRUCTURE. |
| ENGINEER TO COORDINATE COMPLETE ANALYSIS AND |
| DETAILS/SPECIFICATIONS WITH THE PROPOSED INSTALLATION |
| ON THE EXISTING FLAT ROOF AS SPECIFIED BY THE |
| CONTRACTOR SUBMITTING THE PERMIT APPLICATION. |
| NOTE: EXISTING ROOF WAS REPLACED IN 2003. UPLIFT TEST |
| MAY BE REQUIRED TO DEMONSTRATE THAT EXISTING ROOF |
| MEMBRANE WILL RESISTS THE ADDITIONAL WIND LOADS. |
| |
| |
| ORIGINAL COMMENT: |
| 3- ENGINEER OF RECORD NEEDS TO PROVIDE ALL HIS |
| INFORMATION ON THE TITLE BLOCK OF ALL DRAWINGS AS |
| REQUIRED BY SEC. 61G15-23.001(4) F.A.C. |
| |
| RESPONSE: |
| ENGINEER'S INFORMATION IS NOT PROVIDED ON THE TILE |
| BLOCK OF DRAWINGS SUBMITTED. |
| |
| |
| ORIGINAL COMMENT: |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| SEC. 61G20-3.001 F.A.C. FOR: |
| A) ROOF SOLAR PEDESTAL SPECIFIED ON PLANS. |
| |
| RESPONSE: |
| ONE ONE COPY SUBMITTED. NEED TWO COPIES. |
| |
| ORIGINAL COMMENT: |
| B) FOAM ADHESIVE SPECIFIED ON PLANS. NEED PRODUCT |
| APPROVAL FOR FOAM ADHESIVE LISTING THE SURFACE WHERE |
| THE FOAM IS GOING TO BE ADHERED TO. |
| |
| RESPONSE: |
| NEED PRODUCT APPROVAL LISTING THE SURFACE WHERE THE |
| FOAM IS GOING TO BE ADHERED TO. PRODUCT APPROVAL |
| SUBMITTED IS FOR INSTALLATION ON ROOF TILE UNDERLAYMENT |
| ONLY. |
| |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |