2019-08-14 12:55:41 | RESIDENTIAL (R3) BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- STRUCTURAL PLANS SUBMITTED ARE FOR THE INSTALLATION |
| OF SOLAR PV SYSTEMS ON ROOFS WITH ROOF TILES. THIS IS A |
| HOUSE WITH ROOF SHINGLES. THE PROPOSED INSTALLATION |
| DOESN'T MATCH ACTUAL CONDITIONS. REVISE AS REQUIRED. |
| SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- STRUCTURAL ATTACHMENT TO THE ROOF OF THE HOUSE IS |
| NOT CLEAR. FLORIDA PRODUCT APPROVAL FL21074.R4 |
| REFERENCED ON DRAWING S-03 IS ONLY FOR THE "ROOF SOLAR |
| PEDESTAL". THIS PRODUCT APPROVAL ONLY EVALUATES THE |
| SOLAR PEDESTAL ADHERED TO TOP OF FOAM ADHESIVE. ALSO, |
| THE DESIGN OF THE ROOF ADHESIVE TO THE BUILDING |
| STRUCTURE IS OUTSIDE THE SCOPE OF THIS PRODUCT |
| APPROVAL. SEE ITEMS # 12.1 AND 12.2 OF THE LIMITATIONS |
| AND CONDITIONS OF USE ON PAGE 3 OF 7 OF THIS PRODUCT |
| APPROVAL. ENGINEER OF RECORD NEEDS TO PROVIDE COMPLETE |
| DESIGN ANALYSIS AND DETAILS/SPECIFICATIONS SHOWING THE |
| DESIGN ATTACHMENT OF THE FOAM ADHESIVE TO THE BUILDING |
| STRUCTURE. NEED TO SHOW HOW THE SURFACE RECEIVING THE |
| FOAM ADHESIVE WILL TRANSFER THE LOADS. SEC. 107.2.1.2 |
| CITY AMENDMENTS AND SEC. R301.1 FBC-RESIDENTIAL. |
| NOTE: KEEP IN CONSIDERATION THAT THIS HOUSE HAS ROOF |
| SHINGLES. ALSO, NEED PRODUCT APPROVAL FOR FOAM ADHESIVE |
| LISTING THE SURFACE WHERE THE FOAM IS GOING TO BE |
| ADHERED TO. |
| |
| 3- ENGINEER OF RECORD NEEDS TO PROVIDE ALL HIS |
| INFORMATION ON THE TITLE BLOCK OF ALL DRAWINGS AS |
| REQUIRED BY SEC. 61G15-23.001(4) F.A.C. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| SEC. 61G20-3.001 F.A.C. FOR: |
| A) ROOF SOLAR PEDESTAL SPECIFIED ON PLANS. |
| |
| B) FOAM ADHESIVE SPECIFIED ON PLANS. NEED PRODUCT |
| APPROVAL FOR FOAM ADHESIVE LISTING THE SURFACE WHERE |
| THE FOAM IS GOING TO BE ADHERED TO. |
| |
| 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS |
| |
| PLEASE, INSERT CORRECTED PAGES INTO THE SUBMITTAL AND |
| REMOVE/VOID THE PREVIOUSLY REVIEWED SHEETS. PLEASE |
| DON'T STAPLE OLD DRAWINGS/DOCUMENTS . SUBMIT OLD |
| DRAWINGS/DOCUMENTS FOR REFERENCE. |
| |