2019-07-25 16:08:02 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING |
| TEST REPORTS. IT IS RECOMMENDED THAT THIS BE RESOLVED |
| VIA EMAIL PRIOR TO RESUBMITTAL. EMAIL THE NAME OF THE |
| UNDERLAYMENT PROPOSED TO [email protected]. IF THE |
| MANUFACTURER HAS ALREADY PROVIDED THE REQUIRED TEST |
| REPORTS DIRECTLY TO US, TEST REPORTS DO NOT NEED TO BE |
| SUBMITTED WHEN RESUBMITTING. |
| |
| PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| 2. PROVIDE THE VALUE OF THE JOB, INCLUDING MATERIALS |
| PROVIDED BY OTHERS, FBC 109. |
| |
| |