| BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. PROVIDE FLOOR PLAN. SHOW LOCATION OF PROPOSED |
| WINDOWS. |
| FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| 2. PROVIDE WINDOW SCHEDULE. INCLUDE ROUGH OPENINGS AND |
| DESIGN PRESSURE OF EACH OPENING. |
| FBC 107.3.5.3 ? PROVIDE WIND DESIGN LOADS/DESIGN |
| PRESSURES PURSUANT TO FBC-R301.2. |
| |
| 3. DESIGNER TO PRINT NAME AND SIGN PLAN. |
| FBC 107.2.1 ALL INFORMATION, DRAWINGS, SPECIFICATIONS |
| AND ACCOMPANYING DATA SHALL BEAR THE NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR THE DESIGN. (SEE ALSO |
| SECTION 107.3.5) AND F.S. 481.229. |
| |
| 4. PROPOSED WINDOWS ARE NON-IMPACT RATED. SHUTTERS |
| REQUIRED. PROVIDE SHUTTER SCHEDULE. |
| FBC R 301, COMPLETE THE "SCHEDULE FOR INSTALLATION OF |
| OPENING PROTECTIVE DEVICES" OR PROVIDE ALL INFORMATION |
| REQUIRED IN ANOTHER FORMAT (SUCH AS EXCEL SPREADSHEET): |
| |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS?PAGE=2 |
| |
| WHEN COMPLETING THE INSTALLATION SCHEDULE, PLEASE NOTE |
| PAGE 5 OF 5, FACTORS APPLY DEPENDING ON SUBSTRATE, EDGE |
| DISTANCE AND FASTENER. FOR FASTENER, IF USING TAPCON, |
| BE SPECIFIC AS TO WHICH TAPCON (TAPCON W/ADVANCED |
| THREADFORM TECHNOLOGY REQUIRES A .9 FACTOR). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |