Plan Review Notes
Plan Review Notes For Permit 19071005
Permit Number 19071005
Review Stop NFIP
Sequence Number 1
Notes
Date Text
2019-09-26 14:01:16NFIP REVIEW
 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST
 PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE,
 CHAPTER 1 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 BUILDING PLANS EXAMINER, PX3169
 1&2 FAMILY PLANS EXAMINER, SFP306
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 1ST REVIEW
  
 RESULTS: DENIED
  
 YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED
 BELOW.
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 1. BASED ON THE SUBMITTED SURVEY, THIS LOT AND PROPOSED
 IMPROVEMENTS ARE LOCATED IN AN AE FLOOD ZONE WITH A
 BASE FLOOD ELEVATION (BFE) OF 7.0 FEET NAVD.
 2. AS OF OCTOBER 5, 2017, THE FEDERAL EMERGENCY
 MANAGEMENT AGENCY (FEMA) ESTABLISHED A NEW FLOOD
 INSURANCE RATE MAP (FIRM) UTILIZING THE RECENTLY
 COMPLETED FLOOD HAZARD DETERMINATION (FHD) FOR THE CITY
 OF WEST PALM BEACH, FL.
 3. ALL NEW BASE FLOOD ELEVATIONS (BFE) SHALL BE BASED
 ON NAVD88 DATUM. ON AUGUST 23, 2017, THE CITY OF WEST
 PALM BEACH, BY ORDINANCE, ESTABLISHED A TWO FOOT
 FREEBOARD ABOVE THE (BFE).
 4. YOU MAY SUBMIT A SURVEY SHOWING ALL EXISTING AND
 PROPOSED ELEVATIONS BASED ON NAVD88 DATUM PLUS TWO FEET
 OF FREEBOARD OR THE ENGINEER OF RECORD (EOR) MAY ADD A
 STATEMENT TO THE STRUCTURAL PLAN THAT THE DESIGN FLOOD
 ELEVATION (DFE) WILL BE 9.4 FEET NAVD88 BASED ON THE
 (BFE) OF 7.00 FEET FOR FLOOD ZONE AE PLUS A CORRECTION
 FACTOR OF .4 FEET PLUS TWO FEET OF FREEBOARD.
  
 SECTION R322 FLOOD-RESISTANT CONSTRUCTION
  
 R322.1 GENERAL.
 BUILDINGS AND STRUCTURES CONSTRUCTED IN WHOLE OR IN
 PART IN FLOOD HAZARD AREAS (INCLUDING A OR V ZONES) AS
 ESTABLISHED IN TABLE R301.2(1) SHALL BE DESIGNED AND
 CONSTRUCTED IN ACCORDANCE WITH THE PROVISIONS CONTAINED
 IN THIS SECTION. BUILDINGS AND STRUCTURES LOCATED IN
 WHOLE OR IN PART IN IDENTIFIED FLOODWAYS SHALL BE
 DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH ASCE 24.
  
 1612.5 FLOOD HAZARD DOCUMENTATION.
 THE FOLLOWING DOCUMENTATION SHALL BE PREPARED AND
 SEALED BY A REGISTERED DESIGN PROFESSIONAL AND
 SUBMITTED TO THE BUILDING OFFICIAL:
  
 ELEVATION CERTIFICATE - 3 REQUIRED
  
 1. AT PERMITTING ? CONSTRUCTION DRAWINGS
 2. BUILDING UNDER CONSTRUCTION ? PER CHPT. 1, SECTION
 110.3
 3. FINISHED CONSTRUCTION ? PRIOR TO C OF O
  
  
 1. FOR CONSTRUCTION IN FLOOD HAZARD AREAS OTHER THAN
 COASTAL HIGH HAZARD AREAS:
  
 1.1. THE ELEVATION OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AS REQUIRED BY THE FOUNDATION INSPECTION AND
 THE FINAL INSPECTION IN SECTION 110.3.
  
  
  
  