2021-12-22 10:10:05ARMAND PATEL CALLED AND REQUESTED TO HAVE THE GAS
 PORTION REMOVED FROM THE PLANS AND A SEPERATE GAS
 PERMIT AND GAS REVIEW WILL BE SUBMITTED
2019-12-05 11:38:35GAS REVIEW
  
 1) SUBMIT AN EXPANDED GAS RISER FOR THE AREA OF
 REGULATOR "B". IT IS DIFFICULT TO SEE WHERE THE GAS
 LINES CONTINUE/CONNECT AND TO CHECK IF THE LINES ARE
 PROPERLY SIZED. WPB AMEND. TO FBC SEC. 107.2.1.
 2) THE GAS RISER SHOWS A 3/4" SUPPLYING A 352 BTUH
 FUTURE GENERATOR. THIS LINE IS UNDERSIZED PER THE
 REFERENCED GAS TABLE. ALSO, INDICATE THE TYPE ON THE
 GAS RISER FOR THE GENERATOR.
 3) SHOW THE SIZE OF THE PIPE ABOVEGROUND TO THE POOL
 HEATER. WPB AMEND. TO FBC SEC. 107.2.1.
 4) THE GAS RISER SHOWS A 3/4 INCH PE LINE AT .5 PSI TO
 A FUTURE 400 BTUH POOL HEATER. THIS LINE IS UNDERSIZED
 PER THE REFERENCED GAS TABLE.
 5) UNIONS ARE REQUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF ALL REGULATORS. 2017 FBC-GAS SEC.410.2
 (7). INDICATE ON THE RISER.
 6) THE GAS RISER HAS A TABLE FOR REGULATOR "A" &
 REGULATOR "B" BUT THE RISER SHOWS REGULATORS "B" & "C".
 CLARIFY.
 7) CHECK THE BTU LOAD FOR REGULATOR "B". I CALCULATE
 947 BTUH ACCORDING TO THE RISER.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  