Plan Review Notes
Plan Review Notes For Permit 19071003
Permit Number 19071003
Review Stop M
Sequence Number 1
Notes
Date Text
2019-08-21 12:43:46PROVISOS
 NEEDS TO COMPLY WITH 2017 FLORIDA BUILDING CODE - FUEL
 GAS, SIXTH EDITION
 304.5.3.1COMBINING SPACES ON THE SAME STORY.
 EACH OPENING SHALL HAVE A MINIMUM FREE AREA OF 1 SQUARE
 INCH PER 1,000 BTU/H (2,200 MM2/KW) OF THE TOTAL INPUT
 RATING OF ALL APPLIANCES IN THE SPACE, BUT NOT LESS
 THAN 100 SQUARE INCHES (0.06 M2). ONE OPENING SHALL
 COMMENCE WITHIN 12 INCHES (305 MM) OF THE TOP AND ONE
 OPENING SHALL COMMENCE WITHIN 12 INCHES (305 MM) OF THE
 BOTTOM OF THE ENCLOSURE. THE MINIMUM DIMENSION OF AIR
 OPENINGS SHALL BE NOT LESS THAN 3 INCHES (76 MM).
  