2019-08-09 15:14:31CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
 FAC = FLORIDA ADMINISTRATIVE CODE
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOAD CALCULATION FOR PANEL B SHOWS DEMAND FACTORS
 THAT ARE NOT PERMITTED. BECAUSE THIS IS ONLY A 60 AMP
 FEED, DEMAND FACTORS CANNOT BE USED. DEMAND FACTORS ARE
 ONLY PERMITTED WHEN THE FEEDERS ARE RATED 100 AMPS OR
 MORE. THERFORE, THE CIRCUIT BREAKER FOR THIS WOULD
 LIKELY BE OVERLOADED. PROVIDE CORRECTION. NEC 220.82;
 FBC RE E3602.2.1
 2. ORIGINAL RISER DIAGRAM SHOWS A PANEL BEING INSTALLED
 FOR THE POOL EQUIPMENT. THIS HAS BEEN REMOVED FROM THIS
 DRAWING. WITH THE POOL EQUIPMENT NOW BEING FED FROM
 PANEL B, HOW WILL THIS EQUIPMENT HAVE THE REQUIRED
 DISCONNECT WITHIN SIGHT OF THE EQUIPMENT? PROVIDE
 CLARIFICATION. WPB FBC 107.2.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  