2019-08-09 15:14:31 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. LOAD CALCULATION FOR PANEL B SHOWS DEMAND FACTORS |
| THAT ARE NOT PERMITTED. BECAUSE THIS IS ONLY A 60 AMP |
| FEED, DEMAND FACTORS CANNOT BE USED. DEMAND FACTORS ARE |
| ONLY PERMITTED WHEN THE FEEDERS ARE RATED 100 AMPS OR |
| MORE. THERFORE, THE CIRCUIT BREAKER FOR THIS WOULD |
| LIKELY BE OVERLOADED. PROVIDE CORRECTION. NEC 220.82; |
| FBC RE E3602.2.1 |
| 2. ORIGINAL RISER DIAGRAM SHOWS A PANEL BEING INSTALLED |
| FOR THE POOL EQUIPMENT. THIS HAS BEEN REMOVED FROM THIS |
| DRAWING. WITH THE POOL EQUIPMENT NOW BEING FED FROM |
| PANEL B, HOW WILL THIS EQUIPMENT HAVE THE REQUIRED |
| DISCONNECT WITHIN SIGHT OF THE EQUIPMENT? PROVIDE |
| CLARIFICATION. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |