Plan Review Notes
Plan Review Notes For Permit 19071002
Permit Number 19071002
Review Stop B
Sequence Number 1
Notes
Date Text
2019-08-26 11:57:102017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19071002
 ADD: 1675 PALM BEACH LAKES BLVD.
 CONT: TBD. TO BE DETERMINED
 TEL: ???????????
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. AUGUST 26, 2019
 ACTION: DENIED
  
 1) SHEET 001-GN-1 INDICATES THE CANOPY CONSTRUCTION
 TYPE IS A TYPE V CONSTRUCTION. SHEET 007-A-113 HAS A
 NOTE THAT STAINED WOOD T & G ON 5/8 INCH EXTERIOR GRADE
 PLYWOOD SHEATHING.
  
 PLEASE NOTE UNDER THE 2017 FBC-B SECTION 3104.3
 CONSTRUCTION. THE PEDESTRIAN WALKWAY SHALL BE OF
 NON-COMBUSTIBLE CONSTRUCTION. PLEASE REVIEW EXCEPTION #
 2.
 EXCEPTION 2. FIRE-RETARDANT-TREATED WOOD, IN ACCORDANCE
 WITH SECTION 603.1, ITEM 1.3, SHALL BE PERMITTED FOR
 THE ROOF CONSTRUCTION OF THE PEDESTRIAN WALKWAY WHERE
 CONNECTED BUILDINGS ARE A MINIMUM OF TYPE I OR II
 CONSTRUCTION.
  
 2) SHEET S-2.01 INDICATES THE USE OF WELDED AND BOLTED
 CONNECTIONS. THE CONTRACTOR IS REQUIRED TO PROVIDE WELD
 PROCEDURE SPECIFICATIONS & WELDER OPERATOR PERFORMANCE
 QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED
 STANDARDS AT TIME OF INSPECTION. IN ACCORDANCE WITH THE
 AMERICAN WELDING SOCIETY.
 2017 FBC-B 2204.1 WELDING
 2017 FBC-B 2204.2 BOLTING.
 IF THERE IS ANY QUESTIONS ABOUT THE CODE REQUIREMENTS
 FOR THIS SECTION, PLEASE CONTACT THE CHIEF BUILDING
 INSPECTOR KEN CONRAD AT 561-805-6666. THANK YOU
  
 3) SHEET 007-A-113 DETAIL # 2 INDICATES THE
 INSTALLATION OF SINGLE PLY 60 MIL TPO ROOF MEMBRANE
 OVER TAPERED FOAM INSULATION. PLEASE PROVIDE THE
 PRODUCT APPROVAL FOR THE ROOFING AND TAPERED FOAM
 INSULATION.
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3
 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES/ ROOF
 INSULATION.
  
 4) ROOFING: FOR ALL ROOFING PRODUCTS PLEASE IDENTIFY
 ALL ROOFING SUB-SYSTEMS, INSULATION AND THEIR
 ASSOCIATED PRESSURES FOR ROOF ZONE # 1. REVIEW THE
 PRODUCT APPROVAL LIMITATIONS, IF ENHANCED FASTENING IS
 ALLOWED FOR ROOF ZONES 2 & 3. FASTENER DENSITIES SHALL
 BE INCREASED FOR BOTH INSULATION & THE BASE SHEET AS
 CALCULATED IN COMPLIANCE WITH ROOFING APPLICATION
 STANDARDS RAS 117. CALCULATION PREPARED, SIGNED AND
 SEALED BY A FLORIDA REGISTERED PROFESSIONAL ENGINEER OR
 REGISTERED ARCHITECT. 1609.6.4.4.1 COMPONENTS &
 CLADDING.
  
 5) WHEN SUBMITTING THE ROOFING AND INSULATION PRODUCT
 APPROVAL PLEASE VERIFY BEFORE THE PRODUCT APPROVAL IS
 SUBMITTED TO THE BUILDING DEPARTMENT THAT THE DECK
 GAUGE, JOIST SPAN AND ATTACHMENT ARE IN CONFORMANCE
 WITH THE SELECTED ROOFING PRODUCT APPROVAL. 107.2.1.2
 ADDITIONAL INFORMATION IS REQUIRED.
  
 6) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) SHEET S-1.01 UNDER THE HEADING OF SHALLOW
 FOUNDATIONS INDICATES ALL FOOTINGS SHALL BEAR ON SOIL
 OR ROCK PREPARED B PER THE PENDING GEOTECHNICAL REPORT
 THAT WILL BE AVAILABLE.
 2017 FBC-B 1803.5.2 QUESTIONABLE SOIL. WHERE THE
 CLASSIFICATION, STRENGTH OR COMPRESSIBILITY OF THE SOIL
 IS IN DOUBT OR WHERE A LOAD-BEARING VALUE SUPERIOR TO
 THAT SPECIFIED IN THIS CODE IS CLAIMED, THE BUILDING
 OFFICIAL SHALL BE PERMITTED TO REQUIRE THAT A
 GEOTECHNICAL INVESTIGATION BE CONDUCTED.
  
 8) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  