2019-08-24 21:53:13ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 GUEST HOUSE:
  
 1. PROVIDE ACCURATE PANEL SCHEDULES SHOWING OCP, WIRE
 SIZE, AND AFCI/GFCI PROTECTION WHERE APPLICABLE. FBC
 107.2.1 NEC 210.8, 210.12
  
 2. SMOKE DETECTORS AND CARBON MONOXIDE DETECTORS
 REQUIRED. FBC RE 314&315
  
 3. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 4. GARAGE RECEPTACLES MUST BE GFCI PROTECTED NEC 210.8
  
 5. PROVIDE NOTE ON PLAN THAT STATES LOW VOLTAGE AND
 GENERATOR REQUIRES SEPARATE ELECTRICAL PERMITS. FBC
 107.2.1
  
 6. SERVICE RECEPTACLES REQUIRED FOR AHU'S AND A/C
 CONDENSORS NEC 210.63
  
 MAIN HOUSE:
  
 1. PROVIDE ACCURATE PANEL SCHEDULES SHOWING OCP, WIRE
 SIZE, AND AFCI/GFCI PROTECTION WHERE APPLICABLE. FBC
 107.2.1 NEC 210.8, 210.12
  
 2. PROVIDE LOCATIONS ON PLANS OF ALL PANELS SHOWN ON
 ONE-LINE/RISER DIAGRAM. PROVIDE LOCATIONS FOR ALL THREE
 ATS'S, ALL SUB-PANELS, AND POOL PANEL. ALL LOCATIONS
 NOW SHOWN ON PLAN. FBC 107.2.1
  
 3. SMOKE DETECTORS/ CARBON MONOXIDE DETECTORS REQUIRED
 PER FBC RE 314&315. PROVIDE CORRECTION.
  
 4. PROVIDE NOTE ON PLAN THAT STATES LOW VOLTAGE AND
 GENERATOR REQUIRES SEPARATE ELECTRICAL PERMITS. FBC
 107.2.1
  
 5. PROVIDE COMPLIANCE: "A MINIMUM OF 75 PERCENT OF THE
 LAMPS IN PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 BE HIGH-EFFICACY LAMPS OR A MINIMUM OF 75 PERCENT OF
 THE PERMANENTLY INSTALLED LIGHTING FIXTURES SHALL
 CONTAIN ONLY HIGH EFFICACY LAMPS". A NOTE WILL SUFFICE.
 FBC EC R404.1
  
 6. LIGHTING PLAN AND POWER PLAN DO NOT HAVE SAME
 STRUCTURAL LAYOUT. POWER PLAN SHOWS A ROOM ADJACENT TO
 BEDROOM#2 AND BATHROOM #2 BUT IS NOT SHOWN ON LIGHTING
 PLAN?? PROVIDE ACCURATE DRAWINGS SHOWING ALL DOOR AND
 ROOM LOCATIONS THAT MATCH ON BOTH ELEC AND LIGHTING
 PLANS FBC 107.2.1
  
 7. NO ELECTRIC SHOWN FOR A/C CONDENSORS OUTSIDE? FBC
 107.2.1
  
 8. NO LOCATIONS SHOWN FOR AHU'S OR ELECTRIC. FBC
 107.2.1
  
 9. NO ATTIC ACCESS SHOWN? MUST SHOW ATTIC ACCESS WITH
 PROPER ELECTRICAL REQUIRED. FBC 107.2.1
  
 10. MUST HAVE BONDING BRIDGE AT SERVICE. NEC 250.94
  
 11. SERVICE RECEPTACLES REQUIRED FOR AHU'S AND A/C
 CONDENSORS NEC 210.63
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved