Plan Review Notes For Permit 19070947
Permit Number 19070947
Review Stop Z
Sequence Number 1
Notes
Date Text
2019-07-23 17:01:12FAILED
  
 PROVIDE WRITTEN RESPONSES TO COMMENTS.
  
 1) THE LOCATION OF THE POLES ON THE CITY COMMISSION
 APPROVED SITE PLAN AND THE SUBMITTED ELECTRICAL PLANS
 BY EDA DIFFER THAN THE PLANS PROVIDED BY MUSCO. THE
 MUSCO PLANS HAVE THE POLES CLOSER TOGETHER. ALL PLANS
 NEED TO SHOW THE SAME CONDITIONS. IF THE MUSCO PLANS
 WILL BE THE INSTALL VERSION, THEN PRIOR TO FINAL
 INSPECTION, A MINOR AMENDMENT TO REVISE THE CITY
 COMMISSION SITE PLAN IS REQUIRED AND THE ELECTRICAL
 PLAN SITE PLAN NEEDS TO BE CORRECTED PRIOR TO PERMIT
 ISSUANCE.
  
 2) THERE IS ONE LOCATION AT THE SOUTH PROPERTY LINE
 WHERE THE ONE FOOT CANDLE ALLOWANCE IS EXCEEDED. PLEASE
 REVISE THE PLANS ACCORDINGLY.
  
 3) PROVIDE A DRAWING WITH THE EXACT POLE AND FIXTURES
 THAT INCLUDES THE OVERALL HEIGHT OF THE POLE AND THE
 FIXTURES FROM GRADE. THE INFORMATION PROVIDED IN
 APPENDICES E AND G SHOW POLES BUT DO NOT INCLUDE THE
 OVERALL HEIGHT WITH THE FIXTURES FROM GRADE. THE
 OVERALL HEIGHT MAY NOT EXCEED 80 FEET.
  