Plan Review Notes For Permit 19070947 |
Permit Number |
19070947 |
|
Review Stop |
Z |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-23 17:01:12 | FAILED | | | | PROVIDE WRITTEN RESPONSES TO COMMENTS. | | | | 1) THE LOCATION OF THE POLES ON THE CITY COMMISSION | | APPROVED SITE PLAN AND THE SUBMITTED ELECTRICAL PLANS | | BY EDA DIFFER THAN THE PLANS PROVIDED BY MUSCO. THE | | MUSCO PLANS HAVE THE POLES CLOSER TOGETHER. ALL PLANS | | NEED TO SHOW THE SAME CONDITIONS. IF THE MUSCO PLANS | | WILL BE THE INSTALL VERSION, THEN PRIOR TO FINAL | | INSPECTION, A MINOR AMENDMENT TO REVISE THE CITY | | COMMISSION SITE PLAN IS REQUIRED AND THE ELECTRICAL | | PLAN SITE PLAN NEEDS TO BE CORRECTED PRIOR TO PERMIT | | ISSUANCE. | | | | 2) THERE IS ONE LOCATION AT THE SOUTH PROPERTY LINE | | WHERE THE ONE FOOT CANDLE ALLOWANCE IS EXCEEDED. PLEASE | | REVISE THE PLANS ACCORDINGLY. | | | | 3) PROVIDE A DRAWING WITH THE EXACT POLE AND FIXTURES | | THAT INCLUDES THE OVERALL HEIGHT OF THE POLE AND THE | | FIXTURES FROM GRADE. THE INFORMATION PROVIDED IN | | APPENDICES E AND G SHOW POLES BUT DO NOT INCLUDE THE | | OVERALL HEIGHT WITH THE FIXTURES FROM GRADE. THE | | OVERALL HEIGHT MAY NOT EXCEED 80 FEET. | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | [email protected] |
|