Plan Review Notes For Permit 19070831 |
Permit Number |
19070831 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-10-02 08:22:27 | 3202.2 FBC[B]ENCROACHMENTS ABOVE GRADE AND BELOW 8 FEET | | IN HEIGHT. ENCROACHMENTS INTO THE PUBLIC RIGHT-OF-WAY | | ABOVE GRADE AND BELOW 8 FEET (2438 MM) IN HEIGHT SHALL | | BE PROHIBITED EXCEPT AS PROVIDED FOR IN SECTIONS | | 3202.2.1 THROUGH 3202.2.3. DOORS AND WINDOWS SHALL NOT | | OPEN OR PROJECT INTO THE PUBLIC RIGHT-OF-WAY. | | | | THE NEW DOORS THAT ARE BEING INSTALLED ON SOUTH SIDE | | WHERE GLASS BLOCK REMOVED (SF-06 SHEET A-403.0) APPEAR | | TO BE SWINGING INTO THE RIGHT OF WAY. | | PLEASE ADJUST STOREFRONT SYSTEM SO THAT THIS DOES NOT | | OCCUR. | | | | | | PROVISO: | | AIPP COMPLIANCE REQUIRED; VERIFICATION REQUIRED PRIOR | | TO C.O. | | |
|