2019-07-16 19:17:04 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE MAIN ROOF OF THIS RESIDENCE DOES NOT APPEAR TO | | HAVE A ROOF SLOPE OF AT LEAST 2:12, THEREFORE, ASPHALT | | SHINGLES CAN NOT BE USED. R905.2.2 SLOPE. ASPHALT | | SHINGLES SHALL BE USED ONLY ON ROOF SLOPES OF TWO UNITS | | VERTICAL IN 12 UNITS HORIZONTAL (2:12) OR GREATER. FOR | | ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS | | HORIZONTAL (2:12) AND LESS THAN FOUR UNITS VERTICAL IN | | 12 UNITS HORIZONTAL (4:12), DOUBLE UNDERLAYMENT | | APPLICATION IS REQUIRED IN ACCORDANCE WITH SECTION | | R905.1.1. | | | | 2) THE CONTRACT THAT WAS SUBMITTED DOES NOT HAVE THE | | TOTAL PRICE FOR THE WORK SPECIFIED. FBC 109.3 | | | | 3) THE APPLICATION HAS 10 SQUARE FEET AND THE CONTRACT | | HAS 16 SQUARES. CLARIFY. FBC 107.2.1 | | | | |
|