2020-04-07 16:25:38 | REVIEW FBC-2017 MECHANICAL |
| PERMIT- 19070773 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-401: NOTES 3 & 4 APPEAR TO IDENTIFY THE EF-2 |
| ON REVISION 8. REVISION 9 HAS THE SAME NOTES 3 & 4 |
| POINTING AT 2 CIRCLES, PLEASE CLARIFY REVISION 9 |
| DRAWINGS. FBC WPB 107.2.1 |
| 2) SHEET M-401: NOTE 19 IS FOR AN EXHAUST FAN IN THE |
| GENERATOR ROOM, NOTE 1 IS FOR A LOUVER IN THE WALL OF |
| THE GENERATOR ROOM. THIS LOUVER SHOWS THE AIR BEING |
| EXHAUSTED OUT. WOULD THIS NOT BE AN INTAKE FOR THE ROOM |
| AND EXHAUST FAN? FBC WPB 107.2.1 |
| 3) SHEET M-401: PLEASE SPEC OUT THE LOUVER THAT THE |
| EXHAUST FAN DUCT (NOTE 20) IS CONNECTED TO. FBC WPB |
| 107.2.1 |
| 4) SHEET M-401: NOTES 14 & 15 ARE NEW. PLEASE SUBMIT A |
| DRAWING SHOWING THIS COMPLETE PIPING SYSTEM INCLUDING |
| WHERE IT ORIGINATES FROM. FBC WPB 107.2.1 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD |
| SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER |
| SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN |
| THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS |
| PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS |
| PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR |
| UPDATED. |
| |
| |