Plan Review Notes
Plan Review Notes For Permit 19070773
Permit Number 19070773
Review Stop M
Sequence Number 2
Notes
Date Text
2020-04-07 16:25:38REVIEW FBC-2017 MECHANICAL
 PERMIT- 19070773
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-401: NOTES 3 & 4 APPEAR TO IDENTIFY THE EF-2
 ON REVISION 8. REVISION 9 HAS THE SAME NOTES 3 & 4
 POINTING AT 2 CIRCLES, PLEASE CLARIFY REVISION 9
 DRAWINGS. FBC WPB 107.2.1
 2) SHEET M-401: NOTE 19 IS FOR AN EXHAUST FAN IN THE
 GENERATOR ROOM, NOTE 1 IS FOR A LOUVER IN THE WALL OF
 THE GENERATOR ROOM. THIS LOUVER SHOWS THE AIR BEING
 EXHAUSTED OUT. WOULD THIS NOT BE AN INTAKE FOR THE ROOM
 AND EXHAUST FAN? FBC WPB 107.2.1
 3) SHEET M-401: PLEASE SPEC OUT THE LOUVER THAT THE
 EXHAUST FAN DUCT (NOTE 20) IS CONNECTED TO. FBC WPB
 107.2.1
 4) SHEET M-401: NOTES 14 & 15 ARE NEW. PLEASE SUBMIT A
 DRAWING SHOWING THIS COMPLETE PIPING SYSTEM INCLUDING
 WHERE IT ORIGINATES FROM. FBC WPB 107.2.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE OLD
 SHEETS FROM THE PLAN SETS, BIND THEM TOGETHER
 SEPARATELY AND MARK VOID OR OLD ON THEM. PLEASE RETAIN
 THEM FOR REFERENCE WITH THE NEW SUBMITTED PLANS. THIS
 PROCESS WILL ALSO APPLY TO ANY DOCUMENTS SUCH AS
 PRODUCT APPROVALS OR CALCULATIONS BEING REPLACED OR
 UPDATED.
  
  