2019-08-09 15:02:101ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19070773
 8/9/2019
  
 CODES IN EFFECT:
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEETS M-101, 102, 103, & 104: THERE ARE MISSING
 FIRE DAMPERS WHERE DUCTS ARE PENETRATING THE FIRE-RATED
 MECHANICAL ROOM/CORRIDOR WALLS. THERE ARE ONLY
 MOTORIZED DAMPER SYMBOLS AT THESE LOCATIONS.
 2) M-401: THE GENERATOR ROOM MAKEUP AIR OPENING IS
 MISLABELED AS AN EXHAUST OUTLET- SEE NOTE #5.
 3) THE EXHAUST DUCT FROM THE TANK ROOM THAT IS
 PENETRATING THE FIRE-RATED GARAGE WALL AND RUNNING
 THROUGH THE GARAGE MUST BE HOUSED IN A FIRE- RATED
 ENCLOSURE FROM THE POINT OF PENETRATION TO THE OUTLET-
 SECTION 510.7.3 FB C M.
  
 510.7.3 WALL ASSEMBLIES.
 HAZARDOUS EXHAUST DUCT SYSTEMS THAT PENETRATE
 FIRE-RESISTANCE-RATED WALL ASSEMBLIES SHALL BE ENCLOSED
 IN FIRE-RESISTANCE-RATED CONSTRUCTION FROM THE POINT OF
 PENETRATION TO THE OUTLET TERMINAL, EXCEPT WHERE THE
 INTERIOR OF THE DUCT IS EQUIPPED WITH AN APPROVED
 AUTOMATIC FIRE SUPPRESSION SYSTEM. DUCTS SHALL BE
 ENCLOSED IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 BUILDING REQUIREMENTS FOR SHAFT CONSTRUCTION AND SUCH
 ENCLOSURE SHALL HAVE A MINIMUM FIRE-RESISTANCE RATING
 OF NOT LESS THAN THE HIGHEST FIRE-RESISTANCE-RATED WALL
 ASSEMBLY PENETRATED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401