Plan Review Notes For Permit 19070754 |
Permit Number |
19070754 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-07-29 15:05:27 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE THE PLAN TO SHOW OCCUPANCY CLASSIFICATION | | (USE) AND OCCUPANT LOAD FOR THE ROOM WHICH THE DOOR | | SERVES, FBC B 1010.1.10. IT IS NOT CLEAR IF PANIC BARS | | ARE REQUIRED. | | | | 2. I WAS UNABLE TO LOCATE AN ADA THRESHOLD DETAIL IN | | THE PRODUCT APPROVAL. PLEASE INDICATE, PROVIDE A | | PRODUCT APPROVAL WHICH INCLUDES THIS AS AN OPTION AND | | INDICATE, OR PROVIDE INFORMATION AS TO WHY THIS IS NOT | | APPLICABLE, FBC A 403.1, 303.3. | | | | 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A | | COMPLETED RESUBMITTAL FORM, VIA EMAIL TO | | [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT | | NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE | | RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: | | | | HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B | | UILDING-PERMIT-FORMS | | | | | | |
|