Plan Review Notes
Plan Review Notes For Permit 19070754
Permit Number 19070754
Review Stop B
Sequence Number 1
Notes
Date Text
2019-07-29 15:05:27****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE THE PLAN TO SHOW OCCUPANCY CLASSIFICATION
 (USE) AND OCCUPANT LOAD FOR THE ROOM WHICH THE DOOR
 SERVES, FBC B 1010.1.10. IT IS NOT CLEAR IF PANIC BARS
 ARE REQUIRED.
  
 2. I WAS UNABLE TO LOCATE AN ADA THRESHOLD DETAIL IN
 THE PRODUCT APPROVAL. PLEASE INDICATE, PROVIDE A
 PRODUCT APPROVAL WHICH INCLUDES THIS AS AN OPTION AND
 INDICATE, OR PROVIDE INFORMATION AS TO WHY THIS IS NOT
 APPLICABLE, FBC A 403.1, 303.3.
  
 3. YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A
 COMPLETED RESUBMITTAL FORM, VIA EMAIL TO
 [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT
 NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE
 RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE:
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  
  