2019-07-22 10:56:15 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) THE APPLICATION INDICATES "CONSTRUCTION TRAILER |
| TEMPORARY FENCE" |
| |
| THERE IS NO CLEAR INDICATION OF THE LOCATION OF THE |
| TRAILER. |
| |
| PLEASE REVIEW AND CLARFY THE INTENT OF THE APPLICATION; |
| IF FOR A TRAILER AND FENCE, PLEASE PROVIDE EXACT |
| LOCATION OF THE CONSTRUCTION TRAILER WITH DIMENSIONS TO |
| PROPERTY LINES, NEIGHBOR BUILDINGS, PROPOSED BUILDING, |
| ETC. |
| |
| |
| |
| 2) THERE IS A GATE INDICATED IN THE MIDDLE OF THE |
| VACANT FIELD. THERE IS NO FD ACCESS ROAD INTO THE |
| PROPSED FENCED SITE. |
| |
| PER NFPA 1 |
| |
| 18.2.3 FIRE DEPARTMENT ACCESS ROADS. |
| 18.2.3.1 REQUIRED ACCESS. |
| 18.2.3.1.1 APPROVED FIRE DEPARTMENT ACCESS ROADS SHALL |
| BE PROVIDED |
| FOR EVERY FACILITY, BUILDING, OR PORTION OF A BUILDING |
| HEREAFTER |
| CONSTRUCTED OR RELOCATED. |
| 18.2.3.1.2 FIRE DEPARTMENT ACCESS ROADS SHALL CONSIST |
| OF ROADWAYS, FIRE |
| LANES, PARKING LOT LANES, OR A COMBINATION THEREOF. |
| |
| 18.2.3.4.1 DIMENSIONS. |
| 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| UNOBSTRUCTED |
| WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 3) THERE ARE NO DIMENSIONS INDICATED FOR THE GATE. |
| |
| 18.2.3.4.1 DIMENSIONS. |
| 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| UNOBSTRUCTED |
| WIDTH OF NOT LESS THAN 20 FT (6.1 M). |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 4) KNOX PADLOCKS ARE RECOMMENDED FOR EACH TO BE USED IN |
| CONJUCTION WITH YOUR LOCKS SO YOUR LOCK OR CHAIN WILL |
| NOT BE CUT IN THE EVENT OF NEEDED EMERGENCY INCIDENT |
| ACCESS. |
| |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |