Plan Review Notes
Plan Review Notes For Permit 19070731
Permit Number 19070731
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-07-18 15:02:06THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
 1) THE GATES INDICATED ARE REQUIRED TO BE 20' FOR FIRE
 DEPARTMENT ACCESS IN THE EVENT OF EMERGENCY.
  
 PER NFPA 1
  
 18.2.3.4.1 DIMENSIONS.
 18.2.3.4.1.1 FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN
 UNOBSTRUCTED
 WIDTH OF NOT LESS THAN 20 FT (
  
 AND
  
 NFPA 241
  
 7.5.5 ACCESS ROADWAYS.
 7.5.5.1 EVERY BUILDING SHALL BE ACCESSIBLE BY FIRE
 DEPARTMENT
 APPARATUS BY MEANS OF ROADWAYS HAVING AN ALL-WEATHER
 DRIVING
 SURFACE OF NOT LESS THAN 6.1 M (20 FT) OF UNOBSTRUCTED
 WIDTH, HAVING
 THE ABILITY TO WITHSTAND THE LIVE LOADS OF FIRE
 APPARATUS, AND
 HAVING A MINIMUM OF 4.1 M (13 FT 6 IN.) OF VERTICAL
 CLEARANCE.
 7.5.5.2 ACCESS FOR USE OF FIRE DEPARTMENT APPARATUS
 SHALL BE
 PROVIDED TO THE IMMEDIATE JOB SITE AT THE START OF THE
 PROJECT
 AND MAINTAINED UNTIL COMPLETION.
  
 PLEASE ENSURE COMPLIANCE.
  
  
  
 2) IT IS STRONGLY RECOMMENDED, NOT REQUIRED, THAT A
 KNOX PADLOCK BE PROVIDED FOR 24HR EMERGENCY ACCESS.
  
 THE KNOX PADLOCK CAN BE USED IN COMBINATION WITH YOUR
 PADLOCK FOR ACCESS AND SECURITY WHEN THE INCIDENT IS
 COMPLETE.
  
 WEST PALM BEACH FIRE RESCUE KNOX PADLOCKS CAN BE
 PURCHASED AT HTTPS://WWW.KNOXBOX.COM/
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  