2019-07-23 14:10:11 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1.FBC B 107.2.1. PLEASE CORRECT THE FOLLOWING; ON THE |
| SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| ASSEMBLIES: COLUMN HEADING ?SHUTTER SPAN?; SEE TYPICAL |
| (1) HV BLADE SHUTTER ELEVATION; SHEET 5 OF PRODUCT |
| APPROVAL FL1850. COLUMN HEADING ?ANCHOR SPACING?; |
| PROVIDE INFORMATION FROM PAGE 12 OF PRODUCT APPROVAL |
| FL1850 TAPCON W/ADVANCED THREADFORM TECHNOLOGY REQUIRES |
| A .9 FACTOR... COLUMN HEADING ?SHUTTER INSTALLED |
| VERTICAL/HORIZONTAL?: ACCORDION SHUTTERS ARE INSTALLED |
| VERTICALLY AS PER PRODUCT APPROVAL FL1580. |
| 2. FBC B 107.2.1. PLEASE VERIFY THE INFORMATION ON THE |
| SCHEDULE FOR INSTALLATION OF PROTECTIVE DEVICES OR |
| ASSEMBLIES FOR PRODUCT APPROVAL FL11291. EXAMPLE: PAGE |
| 13 TABLE 4 CONCRETE ?? & 5/16? ELCO ULTRACON SPANS |
| 16?-0 < 16?-6? 40 (PSF) ANCHOR SPACING IS 9.0?. PLEASE |
| NOTE SCREEN PANELS CAN BE MOUNTED VERTICALLY OR |
| HORIZONTAL. PLEASE USED APPROPRIATE INSTALLATION METHOD |
| AND SPAN. |
| |