2019-07-24 15:42:21FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
  
 MAIN TO DOCK TO MEET 555.3 GFCI PROTECTION
 REQUIREMENTS.
  
 FAULT CURRENT CALCULATION REQUIRED FOR THE SERVICE.
 110.9, 10
  
 MAIN FEEDING DOCK IS 150A WITH #6 WIRE???
  
 PVC ON UNDERSIDE OF DOCK WILL HAVE TO MEET 352.44
 EXPANSION FITTING REQUIREMENTS.
  
 CONNECTIONS ON DOCK SHALL MEET 555.9
  
 TRANSFORMER AND SERVICE TO MEET 555.5 , AND 555.7